Configuring Iec101 Unbalanced Channel Properties - ABB COM600 3.4 User Manual

Station automation, iec 60870-5-101 master (opc)
Hide thumbs Also See for COM600 3.4:
Table of Contents

Advertisement

3.4.3.2.
24
Station Automation COM600 3.4
IEC 60870-5-101 Master (OPC) User's Manual
Property / Para-
Value or Value range/ Default
meter
RTS Keep Up Pad-
0...255
ding Characters
Default: 0
Single Char
Enabled
Response
Disabled
Default: Disabled
Time Synchroniza-
0...65535
tion Interval
Default: 15
Transmission Wait
0...65535
Delay
Default: 15

Configuring IEC101 Unbalanced Channel properties

The IEC101 Unbalanced Channel properties that can be configured and value ranges for
them can be found in Table 3.4.3.2-1. The actual configuration by using SAB600 is
performed as described in 3.4.1, General about configuring objects.
Table 3.4.3.2-1 IEC101 Unbalanced Channel properties
Property / Para-
Value or Value range/ Default
meter
Basic
Buffer Pool Size
1...250
Default: 50
In Use
In use
Not in use
Default: In use
Protocol
IEC60870-5-101 Unbalanced
Master
Communication
Port
Description
The number of padding characters inser-
ted to the end of telegram to delay the
resetting of RTS signal.
Enables or disables single char responses.
Time synchronization interval in seconds.
Delay in milliseconds between receiving
CTS signal and start of transmission.
Description
Specifies the number of message buffers
reserved for the line. Each Buffer can
contain one message.
Specifies if channel is in use or not.
Protocol
1MRS756703

Advertisement

Table of Contents
loading

Table of Contents