1MRK 511 403-UEN Rev. K
2.
Activate the RESETCOMP input to ensure that the stored values of the compensation factors
are reset to zero.
3.
The logical signals and service values for SCUVPTOV function are available on the local HMI
under: Main menu/Tests/Function status/Unbalance protection/
CapBankVoltageUnbalance(60V, Uub>)/SCUVPTOV(60V, Uub>):x, where x = instance
number.
4.
To store the new values of compensation factors, perform the following steps:
Step No.
4-a
4-b
4-c
* - VT ratios of phase voltages and neutral voltages are considered as 400 kV/110 V. The value of
UBase is considered as 110 V.
The voltage inputs U
input.
5.
Check the respective operation of warning, alarm, and trip.
Bay control REC670
Commissioning manual
UNUnbalAlm> = 2.5% UBase
UNUnbalWrn> = 1.0% UBase
UMin> = 75% UBase
Changes after step 2
Inject constant voltages* of U
63.5∠0° V, U
= 63.5∠240° V,
L2
U
= 63.5∠120° V,
L3
and U
= 0∠0° V in secondary at
N
rated frequency.
Change U
= 2∠0° V in
N
secondary at rated frequency
Activate binary input TRIGCOMP
for 1 s
, U
, and U
L1
L2
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Expected Output
=
UL1, UL2, and UL3 = 230.909 kV
L1
UNSCB = 0.000 kV
UNUNBAL = 0.000 kV
PUNUNBAL= 0.000 %
The following outputs should show the mentioned
values:
K1USED = 0.000
K2USED = 0.000
K1MON = 0.000
K2MON = 0.000
UL1, UL2, and UL3 = 230.909 kV
UNSCB = 7.273 kV
UNUNBAL = 7.273 kV
PUNUNBAL = 3.151 %
The following outputs should show the mentioned
values:
K1USED = 0.000
K2USED = 0.000
K1MON = 0.030
K2MON = 0.030
UL1, UL2, and UL3 = 230.909 kV
UNSCB = 7.273 kV
UNUNBAL = 0.000 kV
PUNUNBAL= 0.000 %
The output COMPEXED should become
HIGH for 100 ms
The output LASTCOMP should display the
date and time of compensation.
The following outputs should show the mentioned
values:
K1USED = 0.030
K2USED = 0.030
K1MON = 0.030
K2MON = 0.030
refer to the bus voltages and U
L3
Testing functionality by secondary injection
refers to the neutral voltage
N
Section 11
141