  • Page 1 ® Relion product family Grid Automation Recloser Protection and Control RER615 Modbus Point List Manual...
  • Page 3 Document ID: 1MRS757822 Issued: 2015-03-06 Revision: B Product version: 1.1 © Copyright 2015 ABB. All rights reserved...
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
  • Page 5 ABB is not liable for any such damages and/or losses.
  • Page 6 (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
  • Page 7: Table Of Contents

    LD0.EFHPTOC1 Non-directional earth-fault protection, high stage (1)..................21 LD0.EFIPTOC1 Non-directional earth-fault protection, instantaneous stage (1)...............22 LD0.FDEFLPDEF1 Directional earth-fault protection, low stage (1)..................22 LD0.FDEFLPDEF2 Directional earth-fault protection, low stage (2)..................22 LD0.DEFHPDEF1 Directional earth-fault protection, high stage (1)..................23 Recloser Protection and Control RER615 Point List Manual...
  • Page 8 LD0.TRPPTRC1 Protection trip conditioning (1)......32 LD0.TRPPTRC2 Protection trip conditioning (2)......32 LD0.MAPGAPC1 Multipurpose analog protection function (1)....................32 LD0.MAPGAPC2 Multipurpose analog protection function (2)....................33 LD0.MAPGAPC3 Multipurpose analog protection function (3)....................33 LD0.MAPGAPC4 Multipurpose analog protection function (4)....................33 Recloser Protection and Control RER615 Point List Manual...
  • Page 9 LD0.XGGIO130 Physical I/O states (BIO card X130) ....50 LD0.XGGIO120 Physical I/O states (AIM card X120)....51 LD0.XGGIO110 Physical I/O states (BIO card X110)....51 LD0.XGGIO100 Physical I/O states (PSM card X100)....52 LD0.XAGGIO130 Physical I/O states (AIM card XA130)....53 Recloser Protection and Control RER615 Point List Manual...
  • Page 10 LD0.CMSTA1 Phase current demand values (1) .......66 CTRL.CBCSWI1 Circuit breaker operation counter (1) ....67 LD0.PEMMTR1 Three-phase energy measurements (1)....68 System diagnostic values............68 Control structure 1...............69 Control structure 2...............69 Control structure 3...............69 Control structure 4...............69 Recloser Protection and Control RER615 Point List Manual...
  • Page 11 CTRL.CBCSWI1 Circuit breaker (1) control........79 LD0.SRGAPC1 Reset SRGAPC1 generic flip-flops....80 LD0.SRGAPC2 Reset SRGAPC2 generic flip-flops....80 LD0.SPCGGIO1 Multipurpose binary outputs (1) .......80 LD0.SPCGGIO2 Multipurpose binary outputs (2) .......81 LD0.SPCRGGIO1 Multipurpose binary outputs (1).....82 Section 3 Glossary.................83 Recloser Protection and Control RER615 Point List Manual...
  • Page 13: Section 1 Introduction

    IED perspective. The system engineer or system integrator must have a basic knowledge of communication in protection and control systems and thorough knowledge of the specific communication protocol. Recloser Protection and Control RER615 Point List Manual...
  • Page 14: Product Documentation

    ABB Website http://www.abb.com/relion. 1.3.2 Document revision history Document revision/date Product version History A/2013-09-17 First release B/2015-03-06 Content updated to correspond to the product version Download the latest documents from the ABB Website http://www.abb.com/substationautomation. Recloser Protection and Control RER615 Point List Manual...
  • Page 15: Related Documentation

    The corresponding parameter values are "On" and "Off". • IED input/output messages and monitored data names are shown in Courier font. When the function starts, the START output is set to TRUE. Recloser Protection and Control RER615 Point List Manual...
  • Page 16: Functions, Codes And Symbols

    1 Wattmetric based earth-fault WPWDE2 Po> -> (2) 32N (2) protection, instance 2 Wattmetric based earth-fault WPWDE3 Po> -> (3) 32N (3) protection, instance 3 Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 17 Multi-purpose protection, instance 5 MAPGAPC5 MAP (5) MAP (5) Multi-purpose protection, instance 6 MAPGAPC6 MAP (6) MAP (6) Fault locator, instance 1 SCEFRFLO1 FLOC (1) 21FL (1) Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 18 Sequence voltage measurement, U1, U2, U0 (B) VSMSQI2 V1, V2, V0 (B) (1) instance 2 Three-phase power and energy PEMMXU1 P, E (1) P, E (1) measurement, instance 1 Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 19 1 Generic up-down counters, instance 1 UDFCNT1 UDCNT (1) UDCNT (1) Generic up-down counters, instance 2 UDFCNT2 UDCNT (2) UDCNT (2) Generic up-down counters, instance 3 UDFCNT3 UDCNT (3) UDCNT (3) Recloser Protection and Control RER615 Point List Manual...
  • Page 21: Section 2 Modbus Data Mappings

    Wattmetric based earth-fault protection WPWDE 5)7)8) 5)7)8) Harmonics based earth-fault protection HAEFPTOC 5)8) 5)8) Negative-sequence overcurrent protection NSPTOC Phase discontinuity protection PDNSPTOC Residual overvoltage protection ROVPTOV 9)10) Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 22 Residual current measurement RESCMMXU Three-phase voltage measurement VMMXU 1(2) Sequence voltage measurement VSMSQI 1(2) Three-phase power and energy measurement PEMMXU Frequency measurement FMMXU Load profile LDPMSTA Other Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 23: Indications

    The signal may have a defined label that is visible, for example, in the Application Configuration tool in PCM600. Description Short description of the signal. See the technical manual for more information. Value Meaning of the value states. Recloser Protection and Control RER615 Point List Manual...
  • Page 24: Common Data 1

    1=Start 3939 246.03 .mcd 3940 246.04 .Str.phsB phsB start 1=Start 3941 246.05 .mcd 3942 246.06 .Str.phsC phsC start 1=Start 3943 246.07 .mcd 3944 246.08 .Op.general OPERATE General operate 1=Operate 3945 246.09 .mcd Recloser Protection and Control RER615 Point List Manual...
  • Page 25: Ld0.Phhptoc1 Phase Overcurrent Protection, High Stage (1)

    1=Start 2913 182.01 .mcd 2914 182.02 .Str.phsB phsB start 1=Start 2915 182.03 .mcd 2916 182.04 .Str.phsC phsC start 1=Start 2917 182.05 .mcd 2918 182.06 .Op.general OPERATE General operate 1=Operate 2919 182.07 .mcd Recloser Protection and Control RER615 Point List Manual...
  • Page 26: Ld0.Fdphlpdoc1 Three-Phase Directional Overcurrent Protection, Low Stage (1)

    1=Start 3019 188.11 .mcd 3020 188.12 .Str.phsB phsB start 1=Start 3021 188.13 .mcd 3022 188.14 .Str.phsC phsC start 1=Start 3023 188.15 .mcd 3024 189.00 .Op.general OPERATE General operate 1=Operate 3025 189.01 .mcd Recloser Protection and Control RER615 Point List Manual...
  • Page 27: Ld0.Dphhpdoc1 Three-Phase Directional Overcurrent Protection, High Stage (1)

    LD0.EFHPTOC1 Non-directional earth-fault protection, high stage (1) BitA RegA IEC 61850 name SA name Description Values LD0.EFHPTOC1 2940 183.12 .Str.general START Stage start 1=Start 2941 183.13 .mcd 2942 183.14 .Op.general OPERATE Stage operate 1=Operate 2943 183.15 .mcd Recloser Protection and Control RER615 Point List Manual...
  • Page 28: Ld0.Efiptoc1 Non-Directional Earth-Fault Protection, Instantaneous Stage (1)

    LD0.FDEFLPDEF2 Directional earth-fault protection, low stage (2) BitA RegA IEC 61850 name SA name Description Values LD0.FDEFLPTOC2 2924 182.12 .Str.general START Stage start 1=Start 2925 182.13 .mcd 2926 182.14 .Op.general OPERATE Stage operate 1=Operate 2927 182.15 .mcd Recloser Protection and Control RER615 Point List Manual...
  • Page 29: Ld0.Defhpdef1 Directional Earth-Fault Protection, High Stage (1)

    LD0.EFPADM2 Admittance-based earth-fault protection (2) BitA RegA IEC 61850 name SA name Description Values LD0.EFPADM2 2844 177.12 .Str.general START Stage start 1=Start 2845 177.13 .mcd 2846 177.14 .Op.general OPERATE Stage operate 1=Operate 2847 177.15 .mcd Recloser Protection and Control RER615 Point List Manual...
  • Page 30: Ld0.Efpadm3 Admittance-Based Earth-Fault Protection (3)

    LD0.WPWDE3 Wattmetric-based earth-fault protection (3) BitA RegA IEC 61850 name SA name Description Values LD0.WPSDE3 3304 206.08 .Str.general START Stage start 1=Start 3305 206.09 .mcd 3306 206.10 .Op.general OPERATE Stage operate 1=Operate 3307 206.11 .mcd Recloser Protection and Control RER615 Point List Manual...
  • Page 31: Ld0.Haefptoc1 Harmonics-Based Earth-Fault Protection (1)

    LD0.NSPTOC2 Negative-sequence overcurrent protection (2) BitA RegA IEC 61850 name SA name Description Values LD0.NSPTOC2 2960 185.00 .Str.general START Stage start 1=Start 2961 185.01 .mcd 2962 185.02 .Op.general OPERATE Stage operate 1=Operate 2963 185.03 .mcd Recloser Protection and Control RER615 Point List Manual...
  • Page 32: Ld0.Pdnsptoc1 Phase Discontinuity Protection (1)

    IEC 61850 name SA name Description Values LD0.PHPTUV1 3138 196.02 .Str.general START General start 1=Start 3139 196.03 .mcd 3140 196.04 .Str.phsA phsA start 1=Start 3141 196.05 .mcd Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 33: Ld0.Phptuv2 Phase Undervoltage Protection (2)

    1=Start 3161 197.09 .mcd 3162 197.10 .Str.phsB phsB start 1=Start 3163 197.11 .mcd 3164 197.12 .Str.phsC phsC start 1=Start 3165 197.13 .mcd 3166 197.14 .Op.general OPERATE General operate 1=Operate 3167 197.15 .mcd Recloser Protection and Control RER615 Point List Manual...
  • Page 34: Ld0.Phptov1 Phase Overvoltage Protection (1)

    LD0.PHPTOV3 Phase overvoltage protection (3) BitA RegA IEC 61850 name SA name Description Values LD0.PHPTOV3 3108 194.04 .Str.general START General start 1=Start 3109 194.05 .mcd 3110 194.06 .Str.phsA phsA start 1=Start Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 35: Ld0.Psptuv1 Positive-Sequence Undervoltage Protection (1)

    3129 195.09 .mcd 3130 195.10 .Str.phsA phsA start 1=Start 3131 195.11 .mcd 3132 195.12 .Str.phsB phsB start 1=Start 3133 195.13 .mcd 3134 195.14 .Str.phsC phsC start 1=Start Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 36: Ld0.Frpfrq1 Frequency Protection (1)

    4010 250.10 .Op.general OPR_OFRQ Operate 1=Operate 4011 250.11 .mcd LD0.FRPTUF2 Underfrequency 4012 250.12 .Op.general OPR_UFRQ Operate 1=Operate 4013 250.13 .mcd LD0.FRPFRC2 Frequency gradient 4014 250.14 .Op.general OPR_FRG Operate 1=Operate 4015 250.15 .mcd Recloser Protection and Control RER615 Point List Manual...
  • Page 37: Ld0.T1Pttr1 Thermal Overload Protection (1)

    General start 1=Start 2965 185.05 .mcd 2966 185.06 .Str.phsA phsA start 1=Start 2967 185.07 .mcd 2968 185.08 .Str.phsB phsB start 1=Start 2969 185.09 .mcd 2970 185.10 .Str.phsC phsC start 1=Start 2971 185.11 .mcd Recloser Protection and Control RER615 Point List Manual...
  • Page 38: Ld0.Trpptrc1 Protection Trip Conditioning (1)

    IEC 61850 name SA name Description Values LD0.MAPGAPC1 3696 231.00 .Str.general START Stage start 1 = Start 3697 231.01 .mcd 3698 231.02 .Op.general OPERATE Stage operate 1 = Operate 3699 231.03 .mcd Recloser Protection and Control RER615 Point List Manual...
  • Page 39: Ld0.Mapgapc2 Multipurpose Analog Protection Function (2)

    BitA RegA IEC 61850 name SA name Description Values LD0.MAPGAPC4 3708 231.12 .Str.general START Start 1 = Start 3709 231.13 .mcd 3700 231.14 .Op.general OPERATE Operate 1 = Operate 3711 231.15 .mcd Recloser Protection and Control RER615 Point List Manual...
  • Page 40: Ld0.Mapgapc5 Multipurpose Analog Protection Function (5)

    LD0.VMHAI1 Voltage total demand distortion (1) Table 52: LD0.VMHAI1 Voltage total demand distortion (1) BitA RegA IEC 61850 name SA name Description Values LD0.VMHAI1 3318 207.06 .Alm.stVal ALARM 1=Alarm 3319 207.07 .mcd Recloser Protection and Control RER615 Point List Manual...
  • Page 41: Ld0.Phqvvr1 Pq - Voltage Variation Signals (1)

    Values CTRL.CBXCBR1 2834 177.02 .ItlByPss.stVal ITL_BYPASS Interlock bypass 1=Bypass 2835 177.03 .mcd 2836 177.04 .BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked 2837 177.05 .mcd 2838 177.06 .BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked 2839 177.07 .mcd Recloser Protection and Control RER615 Point List Manual...
  • Page 42: Ctrl.dcsxswi1 Disconnector Position Indication (1)

    CTRL.ESSXSWI2 Earthing switch indication (2) BitA RegA IEC 61850 name SA name Description Values CTRL.ESSXSWI2 POSITION 2807 175.07 .Pos.stVal.Close Close bit 1=Close 2808 175.08 .Pos.stVal.Open Open bit 1=Open 2809 175.09 .Pos.stVal.Fault Fault bit 1=Pos(00/11) Recloser Protection and Control RER615 Point List Manual...
  • Page 43: Ld0.Darrec1 Ar State (1)

    Reclose ready 1=Ready 3063 191.07 .mcd 3064 191.08 .ActRec.stVal ACTIVE Reclose active 1=Active 3065 191.09 .mcd 3066 191.10 .PrgDsr.stVal DISCR_INPRO Discr.time in progress 1=In progress 3067 191.11 .mcd Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 44: Ld0.Secrsyn1 Synchrocheck (1)

    LD0.SSCBR1 2848 178.00 .OpnAlm.stVal TRV_T_OP_ALM Opn travel time alarm 1=Alarm 2849 178.01 .ClsAlm.stVal TRV_T_CL_ALM Cls travel time alarm 1=Alarm 2850 178.02 .SprChaAlm.stVal SPR_CHR_ALM Spring charge alarm 1=Alarm Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 45: Ld0.Tcsscbr1 Trip Circuit Supervision (1)

    LD0.SEQRFUF1 Fuse failure protection (1) BitA RegA IEC 61850 name SA name Description Values LD0.SEQRFUF1 2996 187.04 .Str.general FUSEF_U Start 1=Start 2997 187.05 .mcd 2998 187.06 .Str3Ph.general FUSEF_3PH 3-phase start 1=Start 2999 187.07 .mcd Recloser Protection and Control RER615 Point List Manual...
  • Page 46: Ld0.Mdsopt1 Generic Operation Time Supervision (1)

    1=Low voltage 3971 248.03 .mcd 3972 248.04 .VDeaPhsB.stVal U_B_BC_DEAD Low phsB or phsBC voltage 1=Low voltage 3973 248.05 .mcd 3974 248.06 .VDeaPhsC.stVal U_C_CA_DEAD Low phsC or phsCA voltage 1=Low voltage 3975 248.07 .mcd Recloser Protection and Control RER615 Point List Manual...
  • Page 47: Ld0.Cmmxu1 Phase Current Limit Supervision (1)

    174.01 .mcd 2786 174.02 .HiWrn.stVal HIGH_WARN High warning 1=Warning 2787 174.03 .mcd 2788 174.04 .LoWrn.stVal LOW_WARN Low warning 1=Warning 2789 174.05 .mcd 2790 174.06 .LoAlm.stVal LOW_ALARM Low alarm 1=Alarm 2791 174.07 .mcd Recloser Protection and Control RER615 Point List Manual...
  • Page 48: Ld0.Vmmxu2 Phase Voltage Limit Supervision (2)

    Input 5 0/1=Off/On 3545 221.09 .mcd 3546 221.10 .Q6.stVal Input 6 0/1=Off/On 3547 221.11 .mcd 3548 221.12 .Q7.stVal Input 7 0/1=Off/On 3549 221.13 .mcd 3550 221.14 .Q8.stVal Input 8 0/1=Off/On 3551 221.15 .mcd Recloser Protection and Control RER615 Point List Manual...
  • Page 49: Ld0.Mvgapc2 Multipurpose Binary Inputs (2)

    3608 225.08 .SPCS05.stVal Ouput state 5 0/1=Off/On 3609 225.09 .mcd 3610 225.10 .SPCS06.stVal Ouput state 6 0/1=Off/On 3611 225.11 .mcd 3612 225.12 .SPCS07.stVal Ouput state 7 0/1=Off/On Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 50: Ld0.Spcggio2 Multipurpose Binary Output States (2)

    Ouput state 5 0/1=Off/On 3641 227.09 .mcd 3642 227.10 .SPCS06.stVal Ouput state 6 0/1=Off/On 3643 227.11 .mcd 3644 227.12 .SPCS07.stVal Ouput state 7 0/1=Off/On 3645 227.13 .mcd Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 51: Ld0.Spcrggio1 Multipurpose Binary Output States (1)

    4090 255.10 .SPCS06.stVal Ouput state 6 0/1=Off/On 4091 255.11 .mcd 4092 255.12 .SPCS07.stVal Ouput state 7 0/1=Off/On 4093 255.13 .mcd 4094 255.14 .SPCS08.stVal Ouput state 8 0/1=Off/On Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 52: Ld0.Spclggio1 Multipurpose Binary Output States (1)

    Ouput state 6 0/1=Off/On 4059 253.11 .mcd 4060 253.12 .SPCS07.stVal Ouput state 7 0/1=Off/On 4061 253.13 .mcd 4062 253.14 .SPCS08.stVal Ouput state 8 0/1=Off/On 4063 253.15 .mcd Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 53: Ld0.Gseggio1 Goose Supervision (1)

    LD0.LEDGGIO1 Indication LED states OFF/ColorX These LED indication points interpret the case when an indication signal is wired to either the OK or ALARM input of the LED function block. The default color for Recloser Protection and Control RER615 Point List Manual...
  • Page 54: Ld0.Ledggio1 Indication Led States Color1/Color2

    OK and ALARM inputs, but inverted to the other. This means that the LED toggles between red and green colors. The default color for ALARM is red and green for OK. Colors can, however, be reconfigured with a setting parameter. Recloser Protection and Control RER615 Point List Manual...
  • Page 55 0/1=Color1/2 3527 220.07 .ISCSO8.stVal LED 8 state 0/1=Color1/2 3528 220.08 .ISCSO9.stVal LED 9 state 0/1=Color1/2 3529 220.09 .ISCSO10.stVal LED 10 state 0/1=Color1/2 3530 220.10 .ISCSO11.stVal LED 11 state 0/1=Color1/2 3531 220.11 <reserved> Recloser Protection and Control RER615 Point List Manual...
  • Page 56: Ctrl.cbcswi1 Circuit Breaker (1) Mom. Position

    BitA RegA IEC 61850 name SA name Description Values LD0.XGGIO130 3184 199.00 .Ind1.stVal X130-Input 1 State 0/1=Off/On 3185 199.01 .mcd 3186 199.02 .Ind2.stVal X130-Input 2 State 0/1=Off/On Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 57: Ld0.Xggio120 Physical I/O States (Aim Card X120)

    IEC 61850 name SA name Description Values LD0.XGGIO110 3216 201.00 .Ind1.stVal X110-Input 1 State 0/1=Off/On 3217 201.01 .mcd 3218 201.02 .Ind2.stVal X110-Input 2 State 0/1=Off/On 3219 201.03 .mcd Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 58: Ld0.Xggio100 Physical I/O States (Psm Card X100)

    203.05 .mcd 3254 203.06 .SPCSO4.stVal X100-Output 4 State 0/1=Off/On 3255 203.07 .mcd 3256 203.08 .SPCSO5.stVal X100-Output 5 State 0/1=Off/On 3257 203.09 .mcd 3258 203.10 .SPCSO6.stVal X100-Output 6 State 0/1=Off/On 3259 203.11 .mcd Recloser Protection and Control RER615 Point List Manual...
  • Page 59: Ld0.Xaggio130 Physical I/O States (Aim Card Xa130)

    User definable registers [Alt.1], visible on 3x and 4x RegA Type Scale IEC 61850 name SA name Description Values < not mappable- not visible > User Register 1 User Register 2 Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 60: User Definable Bits [Alt.2], Visible On 0X,1X,3X And 4X

    < reserved > 128.07 < reserved > 128.08 < reserved > 128.09 < reserved > 128.10 < reserved > 128.11 < reserved > 128.12 < reserved > Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 61: Ssr2 System Status Register (2) Ied Mode And State

    < reserved > 130.03 < reserved > 130.04 Any momentary bit updated 1=Updated 130.05 Any mcd bit set 1=Set 130.06 Device restart bit 1=IED restart 130.07 < reserved > Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 62: Ssr4 System Status Register (4) Data Available 2 (Client- Dependent - User-Definable)

    SSR5 System status register (5) device alive register Table 98: SSR5 System status register (5) device alive register RegA Type Scale IEC 61850 name SA name Description Values Device alive counter 0...65535 Recloser Protection and Control RER615 Point List Manual...
  • Page 63: Ssr6 System Status Register (6) Control Command Status (Client-Dependent)

    Object temperature 9999.9 [C] 0.00…99.99 .TmpRl.mag TEMP_RL Relative temperature -99…999.99 .TmpUsed.mag TEMP_AMB Ambient temperature 0…600,000 .001 .TmmsOp.stVal THERMLEV_ST Est. time to operate [ms] 0…600,000 .001 .TmmsRecEna.stVal THERMLEV_END Est. time to deactivate block [ms] Recloser Protection and Control RER615 Point List Manual...
  • Page 64: Ld0.Cmhai1 Current Total Demand Distortion (1)

    0...500.00 [%] .DmdThdPhV.phsC.cVal. 2175 DMD_TDD_C - phsC 0...500.00 [%] Max demand value: .MaxDmdThdV.phsA.cV 2176 al.mag - phsA 0...500.00 [%] .MaxDmdThdV.phsB.cV 2177 al.mag - phsB 0...500.00 [%] .MaxDmdThdV.phsC.cV 2178 al.mag - phsC 0...500.00 [%] Recloser Protection and Control RER615 Point List Manual...
  • Page 65: Ld0.Phqvvr1 Short Duration Voltage Variations (1)

    Scale IEC 61850 name SA name Description Values LD0.DARREC1 .AutoRecSt.stVal STATUS AR state -2...4 .ShotPntr.stVal SHOT_PTR AR shot pointer value 0...6 .OpCntRs.stVal COUNTER AR operation counter 0...65535 1) See the technical manual. Recloser Protection and Control RER615 Point List Manual...
  • Page 66: Ld0.Darrec1 Autorecloser Counters (1)

    2065 .RmnLifPhB.stVal CB_LIFE_B Remain.life phsB -/+ 9999 2066 .RmnLifPhC.stVal CB_LIFE_C Remain.life phsC -/+ 9999 2067 .AccAPwrPhA.mag IPOW_A Iyt phsA 0...1E6 2068 .AccAPwrPhB.mag IPOW_B Iyt phsB 0...1E6 2069 .AccAPwrPhC.mag IPOW_C Iyt phsC 0...1E6 Recloser Protection and Control RER615 Point List Manual...
  • Page 67: Ld0.Mdsopt1 Generic Operation Time Supervision

    LD0.RESCMMXU1 Residual current measurement (1) Table 111: LD0.RESCMMXU1 Residual current measurement (1) RegA Type Scale IEC 61850 name SA name Description Values LD0.RESCMMXU1 Residual current (1) 0.00...40.0 1000 .A.res.instCVal.mag I0_INST - amplitude [xIn] Recloser Protection and Control RER615 Point List Manual...
  • Page 68: Ld0.Vmmxu1 Voltage Measurements (1)

    [xUn] LD0.VMMXU2 Phase-phase voltage (2) 0.00...4.00 1004 1000 .PPV.phsAB.cVal.mag U_DB_AB - phsAB amplitude [xUn] 0.00...4.00 1005 1000 .PPV.phsBC.cVal.mag U_DB_BC - phsBC amplitude [xUn] 0.00...4.00 1006 1000 .PPV.phsCA.cVal.mag U_DB_CA - phsCA amplitude [xUn] Recloser Protection and Control RER615 Point List Manual...
  • Page 69: Ld0.Vmsqi1 Sequence Of Voltage Measurements (1)

    (low word) .TotVAr.instMag Q_INST Total reactive power Q (high) -/+ 999,999 .TotVAr.instMag (low word) .TotVA.instMag S_INST Total apparent power S (high) -/+ 999,999 .TotVA.instMag (low word) 1000 .TotPF.instMag PF_INST Average power factor -1...1 Recloser Protection and Control RER615 Point List Manual...
  • Page 70: Ld0.Fmmxu1 Frequency Measurement (1)

    0...4.0 [xUn] Update time stamp 1960 - Year - month 1961 - Day - hour 1962 - Minute - second 1963 - Milliseconds 1964 - Time quality 1) See the technical manual. Recloser Protection and Control RER615 Point List Manual...
  • Page 71: Ld0.Vmsta2 Voltage Demand Values (2)

    - (low word) 1949 .MaxVAr.mag - Reactive power Q (high) -/+ 999,999 1950 - (low word) 1951 .MaxVA.mag - Apparent power S (high) -/+ 999,999 1952 - (low word) 1953 < reserved > Recloser Protection and Control RER615 Point List Manual...
  • Page 72: Ld0.Rescmsta1 Residual Current Demand Value (1)

    - phsC amplitude [xIn] Update time stamp 2004 - Year - month 2005 - Day - hour 2006 - Minute - second 2007 - Milliseconds 2008 - Time quality Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 73: Ctrl.cbcswi1 Circuit Breaker Operation Counter (1)

    CTRL.CBCSWI1 Circuit breaker operation counter (1) Table 124: CTRL.CBCSWI1 Circuit breaker operation counter (1) RegA Type Scale IEC 61850 name SA name Description Values CTRL.CBCSWI1 2027 .OpCntRs.stVal Operation counter Operation counter 0…65535 Recloser Protection and Control RER615 Point List Manual...
  • Page 74: Ld0.Pemmtr1 Three-Phase Energy Measurements (1)

    .NumPwrUp.stVal Num of cold starts 0...65535 2055 .WrmStr.stVal Num of warm starts 0...65535 2056 .WacTrg.stVal Num of watchdog resets 0...65535 2057 .NumCmpChg.stVal Num of conf. changes 0...65535 1) See the technical manual. Recloser Protection and Control RER615 Point List Manual...
  • Page 75: Control Structure 1

    Values 8016 Execute register 8017 Password reg 1 acc to setting 8018 Password reg 2 acc to setting 8019 Control register < single bit > 8020 Confirm register < single bit > Recloser Protection and Control RER615 Point List Manual...
  • Page 76: Control Structure 5

    Values 8036 Execute register 8037 Password reg 1 acc to setting 8038 Password reg 2 acc to setting 8039 Control register < single bit > 8040 Confirm register < single bit > Recloser Protection and Control RER615 Point List Manual...
  • Page 77: Device Id String

    SA name Description Values 9211 Control register 0...2 9212 Year 2000...2999 9213 Month 1...12 9214 1...31 9215 Hour 0...23 9216 Minute 0...59 9217 Second 0...59 9218 Millisecond 0…999 1) See the technical manual. Recloser Protection and Control RER615 Point List Manual...
  • Page 78: Time And Reason For Latest Ied Reset

    Timestamp of record 9254 - Year, Month Year/Month 9255 - Day, Hour Day/Hour 9256 - Minute, Second Min/Sec 9257 - Millisecond Millisecond 9258 Event identification 9259 Data object ID1 Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 79 - Record sequence num 1...9999 9286 - Unread records left 0...499 Timestamp of record 9287 - Year, Month Year/Month 9288 - Day, Hour Day/Hour 9289 - Minute, Second Min/Sec Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 80 9317 Event data value 2 Record 7 data to read: If selected 9318 - Record sequence num 1...9999 9319 - Unread records left 0...499 Timestamp of record Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 81 - Minute, Second Min/Sec 9345 - Millisecond Millisecond 9346 Event identification 9347 Data object ID1 9348 Data object ID2 9349 Event data value 1 9350 Event data value 2 Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 82: Fault Record Structure Header

    - Active setting group 1...6 9411 .FltDiskm.mag - Fault distance 0...9999.99 [pu] 9412 < reserved > 9413 < reserved > 9414 < reserved > 9415 < reserved > Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 83: Fault Record Data

    1000 .VoltsBb.mag PhsBb voltage 0...4.00 [xUn] 9445 1000 .VoltsCb.mag PhsCb voltage 0...4.00 [xUn] 9446 1000 .VoltsABb.mag PhsABb voltage 0...4.00 [xUn] 9447 1000 .VoltsBCb.mag PhsBCb voltage 0...4.00 [xUn] Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 84: Controls

    Values LD0.LLN0 2060 2.00 .LEDRs1.Oper.ctlVal Reset indications and LEDs 1=Reset 2061 2.01 .LEDRs2.Oper.ctlVal Reset Alarm LEDs 1=Reset LD0.PEMSTA1 2062 2.02 .RecRs.Oper.ctlVal Reset Power max demands 1=Reset LD0.DARREC1 Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 85: Ld0.Lphd1 Ied Warm Reset (1)

    Select open 1=Select 2049 1.01 .Pos.Oper.ctlVal Select close 1=Select 2050 1.02 .Pos.Oper.ctlVal Cancel selection 1=Cancel 2051 1.03 .Pos.Oper.ctlVal Execute selection 1=Execute 2052 1.04 .Pos.Oper.ctlVal Direct open 1=Open 2053 1.05 .Pos.Oper.ctlVal Direct close 1=Close Recloser Protection and Control RER615 Point List Manual...
  • Page 86: Ld0.Srgapc1 Reset Srgapc1 Generic Flip-Flops

    IEC 61850 name SA name Description Values LD0.SPCGGIO1 2112 5.00 .SPCS01.ctlVal Output 1 control 0/1=Off/On 2113 5.01 .SPCS02.ctlVal Output 2 control 0/1=Off/On 2114 5.02 .SPCS03.ctlVal Output 3 control 0/1=Off/On Table continues on next page Recloser Protection and Control RER615 Point List Manual...
  • Page 87: Ld0.Spcggio2 Multipurpose Binary Outputs (2)

    Output 12 control 0/1=Off/On 2140 6.12 .SPCS13.ctlVal Output 13 control 0/1=Off/On 2141 6.13 .SPCS14.ctlVal Output 14 control 0/1=Off/On 2142 6.14 .SPCS15.ctlVal Output 15 control 0/1=Off/On 2143 6.15 .SPCS16.ctlVal Output 16 control 0/1=Off/On Recloser Protection and Control RER615 Point List Manual...
  • Page 88: Ld0.Spcrggio1 Multipurpose Binary Outputs (1)

    Output 11 control 0/1=Off/On 2427 .SPCS12.ctlVal Output 12 control 0/1=Off/On 2428 .SPCS13.ctlVal Output 13 control 0/1=Off/On 2429 .SPCS14.ctlVal Output 14 control 0/1=Off/On 2430 .SPCS15.ctlVal Output 15 control 0/1=Off/On 2431 .SPCS16.ctlVal Output 16 control 0/1=Off/On Recloser Protection and Control RER615 Point List Manual...
  • Page 89: Section 3 Glossary

    LHMI Local human-machine interface Modbus A serial communication protocol developed by the Modicon company in 1979. Originally used for communication in PLCs and RTU devices. Overcurrent PCM600 Protection and Control IED Manager Recloser Protection and Control RER615 Point List Manual...