2.5.4 Safety communication function (Safety communication model)
This function is not available for the standard model and the Ethernet model.
l Outline
Mitsubishi Electric FR-E800-SCE general-purpose inverters have safety functions to stop the output to motors.
By connecting the inverter with a programmable controller with an Ethernet cable, signal input via communication is
enabled.
Wiring
The following describes terminals related to safety monitoring functions.
Terminal symbol
Terminal function description
SX1
Terminal functions can be selected using Pr.S051 SX1/SX2 terminal function selection.
SX2
SY1
Terminal functions can be selected using Pr.S055 SY1/SY2 terminal function selection.
SY2
Connect this terminal to the power supply common terminal of a transistor output (open collector output)
device, such as a programmable controller, in the source logic to avoid malfunction by undesirable current.
SD
Common terminal for the 24 VDC power supply (terminal PC). Isolated from terminal 5.
Common terminal for SX1 and SX2.
PC
Can be used as a 24 VDC 0.1 A power supply.
SC1
Common terminal for SY1 and SY2.
SC2
l Connection diagram.
Emergency
stop button
Safety programmable
controller
*1
To avoid an electric shock hazard, install a magnetic contactor (MC) at the input side of the inverter.
CPU
+24V
PC
Fuse
CPU
SY1
SC1
SX1
SY2
SC2
SX2
Power
supply
FR-E800-SCE
R/L1 S/L2 T/L3
Gate
Driver
CPU
Gate
Driver
Brake
RA2
RA1
WIRING
MC 
IGBTs
U V W
M
29