Installation Conditions For Outdoor Units; Minimum Distances For Outdoor Units - Panasonic Aquarea WH-ADC0309J3E5 Planning And Installation Manual

Air-to-water heat pumps
Hide thumbs Also See for Aquarea WH-ADC0309J3E5:
Table of Contents

Advertisement

5.2.2.1 Installation conditions for outdoor units

The installation conditions for the outdoor unit are as follows:
● The outdoor unit is designed for outdoor installation only and must not be installed
indoors.
● For condensed water drainage in defrost mode, drainage is recommended via a drain
pipe to the frost-free ground with gravel fill (→
p.
102).
● Maintain the minimum distances (→
p.
101).
● The heat emission of the outdoor unit must not be impeded by additional protection
devices such as awnings or such.
● No objects should be put up that can cause short-circuiting of the exhaust air. Even
when using multiple outdoor units (e.g. in case of heat pump cascades), avoid any air
flow short-circuiting (→
● The operating noise of the outdoor unit must not cause any nuisance to the user or to
neighbours. In certain countries or regions, the installation of air-to-water heat pumps
may require permission. All provisions regarding noise valid at the location must be
taken into account (→
● Additional anti-vibration dampers can be used for enhanced noise isolation.
● Installing an outdoor unit near to the sea, in regions with a high content of sulphur or
at sites where large quantities of oil (e.g. machine oil, etc.) are present, may shorten
its operating lifecycle.
● The outdoor unit is to be installed on a concrete foundation or a stable ground frame,
which may be located on the outer wall of a building. Also, it must be horizontally
aligned and bolted down (ø 10 mm).
● In the case of installation locations experiencing strong winds e.g. on building rooftops
or between buildings, the outdoor unit must be additionally secured by field-supplied
means to prevent tipping over (e.g. by bracing).

5.2.2.2 Minimum distances for outdoor units

Minimum distance of the outdoor unit to the neighbouring walls and objects with
representation of the air flow direction
Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
5.2.2.3 Securing the outdoor unit, p.
5.2.1 Acoustics, p.
1
3
2
5.2.2.3 Securing the outdoor unit,
5.2.2.2 Minimum distances (outdoor units),
97).
1 Minimum distance: 100 mm
2 Minimum distance: 300 mm
1
3 Minimum distance: 1,000 mm
Notes:
The refrigerant pipe connections can be made in four
directions (front, rear, side, bottom).
Note: Schematic figure for explanation purposes only.
Planning
102).
5
101