LG ACHH Series Manual page 103

Air-cooled inverter scroll chiller
Hide thumbs Also See for ACHH Series:
Table of Contents

Advertisement

Error code check
Inverter outdoor fan
Check start
No
Is a contact of IPM power
Fan IPM board replacement
part and signal part normal?
Yes
Is a fan moved
Is a fan moved
No
No
when operating under 700 kPaG of
when operating exceed 2 700 kPaG of
heating low pressure?
cooling high pressure?
Yes
Yes
Fan motor replacement
No problem on an outdoor fan
- 103 -