The phenomena from main component failure
n Fan Motor
Checking Item
(1) The fan motor does not
operate.
Does failure appears
again when starting oper-
ation?
(2) Vibration of the fan motor
is large.
Symptom
1) When power supply is
abnormal
2) For wrong wiring
3) For failure of motor
4) For failure of circuit board
- 44 -
Countermeasure
* Modify connection status in front of or at the rear of
the breaker, or if the power terminal console is at
frosting condition.
* Modify the power supply voltage is beyond specified
scope.
* For following wiring.
1. Check connection status.
2. Check contact of the connector.
3. Check that parts are firmly secured by tightening
screws.
4. Check connection of polarity.
5. Check short circuit and grounding.
* Measure winding resistance of the motor coils.
- 14.2 Ω ± 7 % (@25 ℃)
Replace the circuit board in following procedures if
problems occur again when powering on and if there
are no matters equivalent to items as specified in
above 1) through 4).
(Carefully check both connector and grounding wires
when replacing the circuit board.)
1. Replace only fan control boards.
If starting is done, it means that the fan control
board has defect.
2. Replace both fan control board and the CYCLE
Main Board
If starting is done, it means that the Main CYCLE
Board has defect.
3. If problems continue to occur even after counter-
measure of No.1 and No.2, it means that both
boards has defect.