LG ACHH Series Manual page 85

Air-cooled inverter scroll chiller
Hide thumbs Also See for ACHH Series:
Table of Contents

Advertisement

Error number
Errors
75
Fan CT sensor
(751)
defect
n Failure diagnosis method
Is input voltage normal?
Yes
Is a fan board normal?
Yes
Is an error still
occurred even if the
power is reset?
Yes
Power and installation
environment recheck
Check DC input power 15V on Inverter PCB.
Meaning
In case where micom
input voltage of the top
current at the fan motor is
out of 2.5 V ± 0.3 V range
Confirm input power 15 V wire connection status →
No
Re-assembly and take action when finding a problem
No
Fan board replacement
No
Confirm whether or not a fan board IPM is normal
→ Fan board replacement
Main cause of occurrence
1. Input voltage 15 V abnormality
2. Power wire disconnection and connector contact defect
3. Fan board defect [CT sensor detection part]
4. Inverter board defect [DC power part]
- 85 -
Error code check

Hide quick links:

Advertisement

Table of Contents
loading