Mitsubishi Electric MELSEC iQ-R Series User Manual page 63

Devicenet master/slave module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error
Communication
Error details and causes
code
error code
302FH
25FEH
When the slave function is used, the I/
O communication starts with the data
consistency setting of the master
function enabled.
3030H
The data consistency setting for
refresh and the data consistency
dedicated instruction setting for the
master function or slave function were
enabled simultaneously.
3036H
36FFH
The value of the node address (MAC
ID) of the own node is out of range.
The value of the mode switch is out of
range.
303BH
3BnnH
Two or more same node addresses
(MAC ID) are detected among the
parameters.
3084H
80FEH
The receiving byte of the slave function
set with the parameter is out of range.
3085H
81FEH
The transmit byte of the slave function
set with the parameter is out of range.
3086H
82FEH
The number of the transmit bytes and
the number of the receiving bytes of
the slave function set with the
parameter are both set to 0.
30A0H
A0FEH
When both the master function and
slave function are used, the number of
their I/O points are set to 0.
3220H
The parameter that is not supported is
written.
3C00H
A hardware failure has been detected.
3C01H
3C02H
3C03H
3C0FH
3C10H
3C11H
Action
Set the data consistency setting of the master function to
Disable in "Data Consistency Setting" of "Master/Slave
Function Common Parameters" under "Basic Setting".
Set "Data Consistency Setting" properly in "Master/Slave
Function Common Parameters" under "Basic Setting".
• Set the node address of the own node to 0 to 63 by the
node address setting switch.
• Set the mode switch within 0 to C.
• Set "Node Address" in "Slave Node Information" of
"Master Function Parameters" under "Basic Setting" so
that a node address does not overlap with all other
nodes.
• Set "Node Address" in "Slave Node Information" of
"Master Function Parameters" under "Basic Setting" so
that a node address does not overlap with the node
address of the own node.
Set "Slave Function Input Size" to 0 to 128 in "Slave
Function Parameters" under "Basic Setting".
Set "Slave Function Output Size" to 0 to 128 in "Slave
Function Parameters" under "Basic Setting".
Set "Slave Function Input Size" or "Slave Function Output
Size" to 1 byte or more in "Slave Function Parameters"
under "Basic Setting".
Take one of the following actions in "Basic Setting".
• Set one or more nodes in "Slave Node Information" of
"Master Function Parameters"
• Set "Slave Function Input Size" or "Slave Function
Output Size" to 1 byte or more in "Slave Function
Parameters".
• Check the parameter setting.
• Match the module set by the project of the engineering
tool to the version of the mounted module.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the error
occurs again even after taking the above, the possible
cause is a hardware failure of the module, base unit, or
extension cable. Please consult your local Mitsubishi
representative.
Detection mode
Master
Slave
function
function
4 TROUBLESHOOTING
4.6 List of Error Codes