■Master function I/O address (Un\G1280 to Un\G1531)
The start addresses and sizes (in increments of words) of 'Master function receive data' (Un\G1792 to Un\G2047) and 'Master
function transmit data (Un\G2304 to Un\G2559)' used by each slave node are stored.
The following buffer memory addresses can be used for checking the start address of each node.
Buffer memory address
Un\G1280
Un\G1281
Un\G1282
Un\G1283
Un\G1284
Un\G1285
Un\G1286
Un\G1287
Un\G1531
Master function link scan time area
This area is used to store the link scan time.
■Current link scan time (Un\G1532)
The current link scan time is stored. (Unit: ms)
■Minimum link scan time (Un\G1533)
The minimum link scan time after power-on is stored. (Unit: ms)
■Maximum link scan time (Un\G1534)
The maximum link scan time after power-on is stored. (Unit: ms)
Stored data
1st slave node: Input data start address
1st slave node: Input data size (number of words)
1st slave node: Output data start address
1st slave node: Output data size (number of words)
2nd slave node: Input data start address
2nd slave node: Input data size (number of words)
2nd slave node: Output data start address
2nd slave node: Output data size (number of words)
63rd slave node: Output data size (number of words)