Line Modules
4.3 Active Line Modules
Table 4-16
Technical specifications for Active Line Modules, 500 V to 690 V 3AC
Order number
Rated power
Max. infeed / regenerative feedback
capability at 690V 3AC
Rated DC link current
Base load DC link current
Maximum DC link current
Input current at 690V 3AC
Max. input current at 690V 3AC
Line supply voltages:
- Line voltage
- Line frequency
- Electronic power supply
DC link voltage
Electronic power consumption (24VDC)
Cooling method
DC link capacitance
Charging limit
Power loss
- Air / Coolant
- Total losses
Max. coolant temperature
without derating
with derating
Coolant requirement
2)
Liquid volume of integrated heat exchanger
Typ. pressure drop with volumetric flow
Sound pressure level
Line / load connection
Max. connection cross-section
Line connection (U1, V1, W1)
DC link connection (DCP, DCN)
PE connection
Degree of protection
Dimensions
Width
Height
Depth
Frame size
Weight
UL listed fuse
4)
Number (connected in parallel)
Rated current
Size acc. to DIN 43620-1
Valid for a 5 s duty cycle (overload period) and a duty cycle duration of 300 s based on the base load
1)
DC link current.
This value applies to both coolant options, i.e. water and water / Antifrogen N mixture with 45 %
2)
Antifrogen N.
This value applies to the water coolant option; for other coolant types, see Chapter 8.
3)
In order to build a UL-approved system, it is absolutely essential to use the specified fuses.
4)
4-34
6SL3335–
kW (Pn)
kW
(Pmax)
A
A
A
1)
A
A
V
ACeff
Hz
V
DC
V
DC
A
µF
µF
kW
kW
°C
°C
l/min
dm³
Pa
3)
dB(A)
mm²
mm²
mm²
mm
mm
mm
kg
7TG35–8AA0
7TG41–3AA0
560
1400
840
2100
644
1422
573
1266
966
2133
575
1270
862
1905
500 V 3AC –10% to 690 V 3AC +10% (-15% < 1 min)
1.6
1.46
Liquid cooling with integrated aluminum heat exchanger
96700
19330
38680
77320
0.16 / 5.44
0.56 / 12.92
5.60
13.48
45
45
50
50
16
27
0.74
1.56
70000
70000
54
56
Flange connection with screws M12
4 x 240
4 x 240
Busbar
Busbar
2 x 240
4 x 240
IP00
IP00
265
295
984
1496
545
545
HXL
JXL
110
220
3NE1447-2
3NE1438-2
1
2
670
800
3
3
SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4
47 to 63Hz
24 (20.4 - 28.8)
1.5 x V
line
Chassis Power Units Liquid Cooled