Siemens SINAMICS S120 Equipment Manual page 22

Chassis power units liquid cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

System Overview
1.3 Technical specifications
Cooling circuit (refer to Chapter 8)
Max. system pressure with respect to
atmosphere
Pressure drop at rated volumetric flow
Recommended pressure range
Inlet temperature of liquid coolant
Permissible ambient temperature (air) in
operation
Climatic ambient conditions
Storage
1
Transportation
1
Operation
Environmental class/harmful chemical substances
Storage
1
Transportation
1
Operation
Organic/biological influences
Storage
1
Transportation
1
Operation
Degree of contamination
The Safety-Integrated safety function:
The components must be protected against conducted contamination (e.g. by installing them in a cabinet with degree of
protection IP54B to EN 60529).
Provided that conducted interference can be prevented at the installation site, the degree of protection for the cabinet can
be decreased accordingly.
Installation altitude
Certificates
Conformity
Standards
Approvals
(only up to 600 V 3 AC)
in packaging for transportation
1
1-8
600 kPa
70 kPa
80 kPa to 200 kPa
Dependent on ambient temperature, no condensation permitted
0°C to + 45 °C without derating, >45 °C to + 50 °C see derating
characteristics
(antifreeze essential for temperature range between 0 °C and
5 °C; recommended antifreeze agent: "Antifrogen N" supplied by
Clariant)
Dependent on inlet temperature of liquid coolant, no condensation
permitted:
0 to 45 °C without derating
> 45 °C to 50 °C refer to derating characteristics
Class 1K3 acc. to EN 60721-3-1, temperature –40 °C to +70 °C
Class 2K4 acc. to EN 60721-3-2, temperature –40 °C to +70 °C,
max. air humidity 95 % at +40 °C
Class 3K3 to EN 60721-3-3
Condensation, splashwater and ice formation are not permitted
(EN 60204, Part 1)
Class 1C2 to EN 60721-3-1
Class 2C2 to EN 60721-3-2
Class 3C2 to EN 60721-3-3
Class 1B1 to EN 60721-3-1
Class 2B1 to EN 60721-3-2
Class 3B1 to EN 60721-3-3
2 to EN 61800-5-1
The devices may be operated only in environments with degree of
pollution 2 and without condensation. On control cabinets with forced air
cooling, foreign particles must be filtered out of the inflow air through filter
mats.
To prevent condensation, the devices can be warmed constantly by
heaters.
≤ 2000 m above sea level without derating
> 2000 m above sea level, see derating characteristics
CE (low-voltage and EMC Directives)
EN 61800-5-1, EN 60204-1, EN 61800-3, EN 60146-1-1
cULus (File Nos.: E192450 and E214113), some approvals in preparation
SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4
Chassis Power Units Liquid Cooled