Siemens SINAMICS S120 Equipment Manual page 48

Chassis power units liquid cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line-Side Power Components
2.3 Active Interface Modules
Table 2-12
Technical specifications for Active Interface Modules, 500 V to 690 V 3AC
Order number
Suitable for Active Line Module
Infeed / feedback:
Rated power
Peak power
Rated current
Line supply voltages:
- Line voltage
- Line frequency
- Electronics power supply
- Fan supply voltage
Electronics power consumption
24VDC
Max. fan power consumption
(230VAC)
Bypass contactor
Max. ambient temperature:
Without derating
With derating
Efficiency
Power loss
Cooling air requirement
Sound pressure level at 50/60Hz
Line / load connection
L1, L2, L3 / U2, V2, W2
Max. connection cross-section
PE connection
Max. connection cross-section
Degree of protection
Dimensions
Width
Height
Depth
Frame size
Weight
2-22
6SL3300–
7TG35–8AA0
6SL3335-
7TG35–8AA0
kW (Pn)
560
kW (Pmax)
840
A
575
V
500 V 3AC –10% to 690 3AC V +10% (-15% < 1 min)
ACeff
Hz
V
DC
V
AC
A
0.17
DC
A
4.6
AC
3RT1476-
6AP36
°C
40
°C
55
η
0.99
kW
6.8
m
/s
0.40
3
dB(A)
78 / 80
Flange
connection with
screws M12
6x240mm² per
connection
M12 screw
4x240mm²
IP00
mm
305
mm
1750
mm
545
HI
kg
390
SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4
7TG41–3AA0
7TG41–3AA0
1400
2100
1270
47 to 63Hz
24 (20.4 - 28.8)
230 (195.5 - 264.5)
0.17
4.9
3WL1216-
4BB34-4AN2-Z
Z=C22
40
55
0.99
9.6
0.40
78 / 80
Flange
connection with
screws M12
6x240mm² per
connection
M12 screw
4x240mm²
IP00
505
1750
545
JI
620
Chassis Power Units Liquid Cooled