Siemens SINAMICS S120 Equipment Manual page 129

Chassis power units liquid cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Maximum output frequencies achieved by increasing the pulse frequency
By multiplying the rated pulse frequency with a multiple integer, the following output
frequencies can be achieved taking into account the derating factors in Table 5-11 and
Table 5-12:
Table 5-13
Due to the closed-loop control, the maximum output frequency is limited to 300 Hz.
1)
Chassis Power Units Liquid Cooled
SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4
Maximum output frequencies achieved by increasing the pulse frequency
Pulse frequency
[kHz]
1.25
2
2.5
4
5
Maximum output frequency
[Hz]
100
160
200
300
1)
300
1)
Motor Modules
5.6 Technical specifications
5-25