Motor Modules
5.6 Technical specifications
5.6.3

Parallel switching of Motor Modules

The following rules must be followed for parallel switching of Motor Modules:
• Up to four identical Motor Modules can be switched parallel.
• Parallel switching can only be implemented with a common Control Unit.
• The length of the motor supply lines must be the same (symmetric structure).
• The motor modules must be supplied by a common intermediate circuit.
• For motors with a development system supply line with a minimum line length must be
used, the respective line lengths are shown in the tables below.
• A derating factor of 5 % must be taken into account, regardless of the number of Motor
Modules switched in parallel.
Minimum line lengths for parallel switching and connection to a motor with development system
Attention
The minimum motor line lengths shown in the tables below must be complied with for parallel
switching of two or more Motor Modules, and connection to a motor with a development
system. If the required line length cannot be achieved in the application then a motor reactor
must be provided.
Table 5-14
6SL3325-1TE32-1AA0
6SL3325-1TE32-6AA0
6SL3325-1TE33-1AA0
6SL3325-1TE35-0AA0
6SL3325-1TE36-1AA0
6SL3325-1TE38-4AA0
6SL3325-1TE41-0AA0
6SL3325-1TE41-4AA0
Table 5-15
6SL3325-1TG31-0AA0
6SL3325-1TG31-5AA0
6SL3325-1TG32-2AA0
6SL3325-1TG33-3AA0
6SL3325-1TG35-8AA0
6SL3325-1TG38-1AA0
6SL3325-1TG41-0AA0
6SL3325-1TG41-3AA0
5-26
Motor Modules, 510 V - 720 V DC
Order number
Power [kW]
Motor Modules, 675 V - 1080 V DC
Order number
Power [kW]
Output current [A]
110
210
132
260
160
310
250
490
315
605
450
840
560
985
800
1405
Output current [A]
90
100
132
150
200
215
315
330
560
575
800
810
1000
1025
1200
1270
SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4
Minimum line length [m]
30
27
20
15
13
9
8
5
Minimum line length [m]
90
70
50
30
20
15
10