Air Via Capillary Tubes - Siemens FDA2 Series Planning, Mounting

Pipe system for aspirating smoke detectors
Table of Contents

Advertisement

3
System description
Air aspiration

3.1.3 Air via capillary tubes

18 | 48
The aspirating hole can be connected to the room being monitored via a capillary
tube.
The number, distribution, and diameter of the aspirating holes in the pipes must be
planned individually for each application.
Examples
Aspirate air in control cabinets.
Mount the pipe system in a false ceiling and aspirate the air in the room below
it.
Fig. 6: Pipe system with capillary tube
Planning capillary tubes
Take note of the following:
Inner diameter of capillary tubes 5...7 mm
All capillary tubes in the pipe system must be the same length
Maximum length of capillary tubes 8000 mm
If air from separate control cabinets is to be aspirated via the capillary tubes,
take note of the following:
Direction of airflow in the control cabinet due to ventilation
Airflow conditions in the control cabinet in the event of fire
Always use the software 'FXS2056 ASD Asyst‑Tool V3' to plan the pipe system –
this will ensure you achieve the optimum design.
A6V11783979_en--_a