Heater Specifications; Tec04C Specifications - Huawei Telecom Power TP48200A-HX09A3 User Manual

Table of Contents

Advertisement

TP48200A-HX09A3, TP48200A-HX09A4,
TBC300A-DCA3, TBC300A-DCA5 and
TBC300A-TCA2 Telecom Power
User Manual
Item
Installation mode
Maintenance mode
Cable routing
A.5 Heater Specifications
Table A-5 Heater specifications
Item
Input voltage
Voltage frequency
Operating temperature
Heater start and stop temperature
Operating humidity
Heating power
A.6 TEC04C Specifications
Table A-6 TEC04C specifications
Item
Rated voltage
Rated cooling capacity (L32/L32)
Heating capacity
Rated Cooling Power Consumption
Operating environment
Relative humidity
Issue 04 (2019-11-15)
Specifications
TP48200A-HX09A3 and TP48200A-HX09A4: installed on the
floor, installed against the wall, or stacked on a battery cabinet
TBC300A-DCA3, TBC300A-DCA5, and TBC300A-TCA2:
installed on the floor, installed against the wall, or stacked on a
battery cabinet
NOTE
When the TBC300A-DCA3 or TBC300A-DCA5 is installed against the wall,
the distance between the rear of the cabinet and the wall must be greater than
or equal to 100 mm.
Operated and maintained from the front
Routed in and out from the bottom
Specifications
220 V AC single-phase or 110 V AC dual-live wire
Rated frequency: 50 Hz or 60 Hz
-40° C to +65° C (-40° F to +149° F)
The heater starts when the temperature is 0° C and stops when the
temperature is 15° C.
5% RH to 95% RH
> 500 W
Specifications
-48 V DC
200 W
> 300 W
300 W
-40° C to +40° C
5%-95% RH