Function
Heating
Figure 3-25 TEC airflow directions

3.9 Sensors and Lamp

Figure 3-26 shows the installation positions of the sensors and lamp.
Issue 04 (2019-11-15)
Working Principle
circulation heat sink to accelerate the airflow. The air absorbs the heat from the external
circulation heat sink and returns to the external environment through the air exhaust
vents on the external circulation heat sink. The heat exchange between the internal and
external environment is implemented so far.
The TCUA control box controls the refrigeration chip in the TEC module to heat the
internal circulating air. The internal circulation fan draws the air inside the battery
compartment into the internal circulation heat sink. The internal circulation heat sink
heats the air and then returns the heated air to the battery compartment through the air
exhaust vents. Meantime, the external circulation fan operates according to control logic
and draws natural air into the external circulation heat sink. The air gives out heat and
returns to the external environment through the air exhaust vents on the external
circulation heat sink.