ABB RELION REX640 Operation Manual page 100

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Troubleshooting
Figure 94: More information about the warning
Table 10: Warning indications and codes
Warning indication
Watchdog reset
Power down det.
DNP3 warning
Dataset warning
Report cont. warning
GOOSE contr. warning
SCL config warning
Logic warning
SMT logic warning
GOOSE input warning
ACT warning
GOOSE rec. warning
AFL warning
SMV warning
Table continues on the next page
100
The warning alarm is only displayed when configured in PCM600 event
filtering.
Warning code
Additional information
10
A watchdog reset has occurred.
11
The auxiliary supply voltage has
dropped too low.
22
Error in the DNP3 communication.
24
Error in the Data set(s).
25
Error in the Report control block(s).
26
Error in the GOOSE control block(s).
27
Error in the SCL configuration file or
the file is missing.
28
29
30
31
Analog channel configuration warn-
ing.
32
33
34
Error in the SMV configuration.
1MRS759118 D