ABB RELION REX640 Operation Manual page 119

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759118 D
Table 16: Protocol control in the protection relay
Parameter
Configuration/Commu-
nication/Protocols/Net-
work1/FTP
Configuration/Commu-
nication/Protocols/Net-
work2/FTP
Configuration/Communica-
tion/Protocols/HMI Port/FTP
Configuration/Communica-
tion/Protocols/Network1/
HTTPS
Configuration/Communica-
tion/Protocols/Network2/
HTTPS
Configuration/Commu-
nication/Protocols/Net-
work1/MMS
Configuration/Commu-
nication/Protocols/Net-
work2/MMS
Configuration/Communica-
tion/Protocols/HMI
Port/MMS
Configuration/Commu-
nication/Protocols/Net-
work1/DNP
Configuration/Commu-
nication/Protocols/Net-
work2/DNP
Configuration/Commu-
nication/Protocols/Net-
work1/Modbus
Configuration/Commu-
nication/Protocols/Net-
work2/Modbus
Configuration/Communica-
tion/Protocols/Network1/
IEC-60870-5-104
Configuration/Communica-
tion/Protocols/Network2/
IEC-60870-5-104
7.4.2.3
Protocol write access rights
Write access rights are configurable for FTP, MMS, and HTTPS protocols in
Configuration > Authorization. The write access parameters are used to narrow
down services that allow setting changes on different network interfaces. Disabling
REX640
Operation Manual
Options
Off
On
Secure (Default)
Off
On
Secure (Default)
Off
On
Secure (Default)
Off
On (Default)
Off
On (Default)
Off
On (Default)
Off
On (Default)
Off
On (Default)
Off
On (Default)
Off
On (Default)
Off
On (Default)
Off
On (Default)
Off
On (Default)
Off
On (Default)
Commissioning
Description
Denies FTP and FTPS
Allows FTP and FTPS
Allows FTPS only
Denies FTP and FTPS
Allows FTP and FTPS
Allows FTPS only
Denies FTP and FTPS
Allows FTP and FTPS
Allows FTPS only
Denies HTTPS
Allows HTTPS
Denies HTTPS
Allows HTTPS
Denies IEC 61850 MMS
Allows IEC 61850 MMS
Denies IEC 61850 MMS
Allows IEC 61850 MMS
Denies IEC 61850 MMS
Allows IEC 61850 MMS
Denies DNP3
Allows DNP3
Denies DNP3
Allows DNP3
Denies Modbus
Allows Modbus
Denies Modbus
Allows Modbus
Denies IEC 60870-5-104
Allows IEC 60870-5-104
Denies IEC 60870-5-104
Allows IEC 60870-5-104