ABB RELION REX640 Operation Manual page 95

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759118 D
Fault
Fault indication
code
Internal Fault
116
COM card error
Internal Fault
-10
SO-relay(s), Slot
C
Internal Fault
-11
SO-relay(s), Slot
E
Internal Fault
-12
SO-relay(s), Slot
A2
Internal Fault
-13
SO-relay(s), Slot
B
Internal Fault
-14
SO-relay(s), Slot
D
Internal Fault
-15
SO-relay(s), Slot
F
Internal Fault
-16
SO-relay(s), Slot
G
Internal Fault
-17
SO-relay(s), Slot
A1
Table continues on the next page
REX640
Operation Manual
Fast self-
Additional
recovery
information
attempt
Runtime error: Er-
Yes
ror in the COM
card.
Runtime error:
Yes
Faulty Signal Out-
put relay(s) in card
located in slot C.
Runtime error:
Yes
Faulty Signal Out-
put relay(s) in card
located in slot E.
Runtime error:
Yes
Faulty Signal Out-
put relay(s) in card
located in slot A2.
Runtime error:
Yes
Faulty Signal Out-
put relay(s) in card
located in slot B.
Runtime error:
Yes
Faulty Signal Out-
put relay(s) in card
located in slot D.
Runtime error:
Yes
Faulty Signal Out-
put relay(s) in card
located in slot F.
Runtime error:
Yes
Faulty Signal Out-
put relay(s) in card
located in slot G.
Runtime error:
Yes
Faulty Signal Out-
put relay(s) in card
located in slot A1.
Slow 10min
self-
recovery
Immediate
(# of
attempts)
IRF-mode
Yes (3)
No
Yes (3)
No
Yes (3)
No
Yes (3)
No
Yes (3)
No
Yes (3)
No
Yes (3)
No
Yes (3)
No
Yes (3)
No
Troubleshooting
Action in permanent fault
state
Restart the relay. If recov-
ered by restarting, contin-
ue relay normal operation.
If not recover by restarting,
exchange the communica-
tion module in slot X000.
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot C.
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot E.
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot A2.
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot B.
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot D.
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot F.
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot G.
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot A1.
95