ABB RELION REX640 Operation Manual page 145

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759118 D
7.5.2.3
Checking GOOSE data
1.
REX640
Operation Manual
On the GOOSE Receiving page, check the GOOSE data that the relay subscribes
from the Ethernet network.
The left side of this page shows a list of devices that send GOOSE messages
to the relay. These devices that publish data for the relay are defined in the
relay configuration. The right side of the page shows the GOOSE data the
relay receives from the network. The data set consists of value and quality
attributes. The received data has status indicators where green means all OK,
yellow warning and red error.
Figure 126: GOOSE Receiving page
Commissioning
145