Commissioning
4.
7.4.2

Communication settings

7.4.2.1
Ethernet ports
The protection relay allows the use of a secondary IP address for the station ports
on the communication modules COM1001...COM1003. This secondary IP network is
assigned to a single Ethernet port and can be used to make separate networks
for different communication protocols or, for example, a separate service network
for configuration purposes. Multicast station/bus communication, such as IEC
61850-9-2 LE sampled values and GOOSE, is only supported on the Network 1
interface. The parameters for setting the secondary IP network are located under
Configuration > Communication > Ethernet > Network 2 address.
116
Technical keys of the IEDs in the PCM600 project are configured to match the
technical keys of the physical IEDs.
For successful protection relay engineering and usage, the workstation firewall
TCP and UDP port configurations should be checked, especially for IEC 61850
and FTP. Other protocols are not used for engineering or they are optional.
Table 14: IP ports used by the relay
Port number
Type
21
TCP
22
TCP
102
TCP
443
TCP
123
UDP
502
TCP
2404
TCP
20000
TCP
20000
UDP
1468
TCP
514
UDP
49220...49235
TCP
Default state
Open
Closed
Open
Open
Client service not active
by default in relay
Closed
Closed
Closed
Closed
Closed
Closed
Closed
1MRS759118 D
Description
Explicit FTP over TLS
SSH (HMI only, normally
closed)
IEC 61850
Web server HTTPS
SNTP
Modbus TCP
IEC 60870-5-104 TCP
DNP3 TCP
DNP3 UDP
CAL
CAL
Ports open on demand for
data transfer when FTP
PASV command is given
REX640
Operation Manual