LUNA2000-100KTL-M1 Smart Power Control System
User Manual
No.
Category
55
56
57
58
59
60
61
62
63
Issue 02 (2023-01-10)
Parameter
Description
VSG inertia time
Specifies the time required for
constant (s)
the virtual rotor of the virtual
synchronous generator to
reach the rated speed from
the static state under the
rated torque.
P-F adjustment
Specifies the frequency
coefficient (%)
deviation corresponding to
the rated active power of the
virtual synchronous generator.
Q-V adjustment
Specifies the voltage
coefficient (%)
deviation corresponding to
the rated reactive power of
the virtual synchronous
generator.
P-V adjustment
Specifies the voltage
coefficient (%)
deviation corresponding to
the rated active power of the
virtual synchronous generator.
Q-F adjustment
Specifies the frequency
coefficient (%)
deviation corresponding to
the rated reactive power of
the virtual synchronous
generator.
VSG output
Corrects the deviation caused
voltage
by the transformer ratio error.
correction
coefficient (%)
VSG output
Specifies the power factor
frequency
that prevents the frequency
damping
change of the virtual
coefficient (%)
synchronous generator.
VSG excitation
Specifies the time required for
time constant
the excitation of the virtual
(s)
synchronous generator to
reach the rated voltage.
VSG excitation
Specifies the power factor
damping
that prevents the voltage
constant (%)
change of the virtual
synchronous generator.
Copyright © Huawei Technologies Co., Ltd.
6 Power-On Commissioning
Remarks
68