Huawei LUNA2000-100KTL-M1 User Manual page 94

Smart power control system
Hide thumbs Also See for LUNA2000-100KTL-M1:
Table of Contents

Advertisement

LUNA2000-100KTL-M1 Smart Power Control System
User Manual
Alarm
Alarm
ID
Name
2035
Grid
Voltage
Imbalance
2036
Grid
Overfreque
ncy
Issue 02 (2023-01-10)
Severi
Possible Cause
ty
Major
Cause ID = 1
The difference between grid
phase voltages exceeds the
upper threshold.
Major
Cause ID = 1
Power grid exception: The
power grid frequency is higher
than the frequency required in
the local standard.
Copyright © Huawei Technologies Co., Ltd.
8 Alarm Reference
Suggestion
1. If the alarm occurs
occasionally, the power grid
may be abnormal
temporarily. The device
automatically recovers after
detecting that the power
grid becomes normal.
2. If the alarm occurs
frequently, check whether
the power grid voltage is
within the normal range. If
not, contact the local power
operator.
3. If the fault persists for a
long time, check the
connection of the AC cable.
4. If the AC cable is correctly
connected and the alarm
persists and affects the
operation of the plant,
contact the local power
operator.
1. If the alarm occurs
occasionally, the power grid
may be abnormal
temporarily. The device
automatically recovers after
detecting that the power
grid becomes normal.
2. If the alarm occurs
frequently, check whether
the power grid frequency is
within the allowed range. If
not, contact the local power
operator. If yes, modify the
power grid overfrequency
protection threshold after
obtaining the consent of the
local power operator.
88