3-17. Input/Output test functions

Line
Access
I
Relay test
This consists of instructing the regulator's relays one by one and checking their outputs. This
enables you to check that the relays are working and that the cabling is correct. Check that each
appliance in the installation is operating correctly.
0: No test, 1: Everything is on STOP, 2: Relay output QX1 : heat pump CC1 (if 1 circuit ) or heat
pump CC2 (if 2 circuits), 3: Relay output QX2 : Electrical back-up (1st stage) or Boiler connection
distribution valve, 4: Relay output QX3 : Electrical back-up (2nd stage) or Boiler connection contact,
5: Relay output QX4 : DHW distribution valve, 6: Relay output QX5 : DHW Electrical back-up, 7:
Relay output QX6 , 8: Relay output QX31 : Heat circ mix valve open Y1 (or control pilot-wire), 9:
Relay output QX32 : Heat circ mix valve close Y2, 10: Relay output QX33 : heat pump CC1 if 2
7700
circuits (mixed circuit, the less hot), 11: Relay output QX34, 12: Relay output QX35 : Swimming
pool distribution valve, 13: Relay output QX21 module 1, 14: Relay output QX22 module 1, 15:
Relay output QX23 module 1, 16: Relay output QX21 module 2, 17: Relay output QX22 module 2,
18: Relay output QX23 module 2, 19: Not used, 20: Not used, 21: Not used
The display shows the "Key" symbol. Pressing the Info button displays "Error 368".
WARNING
The component being tested is receiving electrical power throughout the test.
7710
I
Output UX1 test
7716
I
Output UX2 test
7722
I
Digital output DO2
7723
I
Heat pump D3
Outputs test UX3 ("Inverter"
7724
I
command)
7725
I
Voltage value (UX3)
Sensor temperature BX1 (HP
7804
I
flow temperature)
Sensor temperature BX2 (HP
7805
I
return temperature)
Sensor temperature BX3
7806
I
(DHW temperature)
Sensor temperature BX4
7807
I
(Outside temperature)
Sensor temperature BX21
7830
I
module 1
Sensor temperature BX22
7831
I
module 1
Sensor temperature BX21
7832
I
module 1
Sensor temperature BX22
7833
I
module 2
7858
I
Input signal H3
Input EX1 (Power shedding,
7911
I
EJP)
7912
I
Input EX2 (Tariffs day/night)
7913
I
Input EX3 (External fault)
Input/Output testing is used to ensure that the connected components are in working order.
3-17. Input/Output test functions
Function
Setting range or display
0...100%
0...100%
Off, On
Off, On
0...100%
0...10 V
-28...350°C
-28...350°C
-28...350°C
-28...350°C
-28...350°C
-28...350°C
-28...350°C
-28...350°C
None,
Closed (ooo)
Open (---)
Pulse
Frequency Hz
Voltage V
0, 230 V
0, 230 V
0, 230 V
- (03-55) -
Setting
Factory
increment
setting
No test
1
---
1
---
Off
Off
---
---
---
---
---
---
---
---
---
---
None
---
---
---
3. Function table