Diagnostics Heat Generation Functions - Fujitsu WSYA050ML3 Design & Technical Manual

Table of Contents

Advertisement

3-19. Diagnostics heat generation functions

Line
Access
8400
I
Compressor 1
8402
I
Electrical resistance flow 1
8403
I
Electrical resistance flow 2
8406
I
Condenser pump
8407
S
Speed condenser pump
Return temperature HP
8410
U
Setpoint (flow) HP
Flow temperature HP
8412
U
Setpoint (flow) HP
8413
U
Compressor modulation
8414
I
Modulation electric flow
8425
S
Temperature differential condenser
8450
S
Hours run compressor 1
Locking time Heat Pump
8454
S
Reset? (no, yes)
Counter number of locks HP
8455
S
Reset? (no, yes)
Hours run electric flow
8456
S
Reset? (no, yes)
Start counter electric flow
8457
S
Reset? (no, yes)
8458
I
State smart grid
8460
I
Heat pump throughput
Various setpoints and actual values, relay switch status data can be displayed for purpose of diagno-
sis.
• Heat pump
These lines are used to check the operating mode of the components controlled by heat pump re-
lays. The display "0" means that the associated components are currently disconnected. The dis-
play "1" means that the associated components are currently switched on.
NOTE: This information applies to relays defined as normally open contacts. For normally closed
contacts, the action is reversed.
• Setpoints and measured values
These lines allow the various setpoints and measured values for the heat pump to be viewed.
3-19. Diagnostics heat generation functions
Function
Line
8402
Electric immersion heater 1 flow
8403
Electric immersion heater 2 flow
8406
Condenser pump
Line
8410
Return temperature HP
8412
Flow temperature HP
8413
Compressor modulation
8414
Modulation electric flow
8425
Temperature difference condenser
Setting range or display
Off, On
Off, On
Off, On
Off, On
0...100%
0...140°C
0...140°C
0...140°C
0...140°C
0...100%
0...100%
-50...140°C
00:00
0...2730 h
0...65535
0...2730 h
0...65535
Draw disabled
Draw free
Draw wish
Draw forced
0...65535 l/min
Function
Function
- (03-62) -
Factory
setting
Off
Off
Off
Off
---
---
---
---
---
---
---
---
---
---
---
---
---
Draw free
---
3. Function table

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents