Fujitsu WSYA050ML3 Design & Technical Manual page 91

Table of Contents

Advertisement

• Release
The "Release" setting determines the time program according to which cooling is released.
– 24 h/day (Not recommended): Regardless of the time programs, the temperature of the do-
mestic hot water is continuously maintained at the DHW nominal setpoint temperature.
Example:
– Heating circuit time programs (Not recommended): Depending on the heating circuit time
programs, the DHW setpoint is changed between the DHW temperature nominal setpoint and
the DHW temperature reduced setpoint. The first switch-on point of each phase is advanced by
one hour each time.
Example:
– Time program 4/DHW (Recommended): Time program 4 of the local controller is taken into
account for the DHW mode. The changeover between DHW nominal setpoint and DHW re-
duced setpoint occurs on the changeover times of this program. Thus, domestic hot water
charging takes place independently from the heating circuits.
Example:
– Low-tariff: Released when the low-tariff input is active. (Input EX2)
– Time program 4/DHW or Low-tariff: Released when DHW program is set to "Nominal" or if the
low-tariff input.
3-6. Domestic hot water functions
Line
Release of DHW load
1620
0
0
5 6
0
6
Function
24h/day
Heating circuit time programs
Time program 4/DHW
Low-tariff
Time program 4/DHW or Low-tariff
6
12
18
12
16 17
12
- (03-33) -
24 h
24 h
18
24 h
3. Function table