Dip Switch 3 To Position On And Dip Switch 4 To Position; Dip Switches 1, 2, 3 And 4 To Position On - ABB Arc Guard System TVOC-2 Installation And Maintenance Manual

Hide thumbs Also See for Arc Guard System TVOC-2:
Table of Contents

Advertisement

DIP switch 3 to
position ON and
DIP switch 4 to
position 0.
DIP switches 1, 2,
3 and 4 to position
ON
Set DIP switch 3 to position ON and DIP switch 4 to position 0.
O
5 6 7 8
1 2
3 4
N
• Detectors X1: 1-3 operate trip contact K4.
• Detectors X1: 4-6 operate trip contact K5.
• Detectors X1: 7-10 and all detectors on X2 and X3, operate trip contact K6.
Set DIP switches 1, 2, 3 and 4 to position ON. In this configuration two CSU
are connected.
See more information the chapter "Two (2) CSU connected" on page - 44
O
1 2 3 4
N
• Any detector with combination of over current condition in CSU 21, operates
trip contacts K4 and K5.
• Any detector with combination of over current condition in CSU 22, operates
trip contacts K5 and K6.
43
44
53
54
63
64
43
K4
K5
K6
Trip
Trip
Trip
Trip
X3
X3
X2
X2
X1
X1
43 44
53 54
63 64
K4
K5
K6
Trip
Trip
Trip
5 6 7 8
X3
X2
X1
CSU
Installation
44
53
54
63
64
43
44
53
54
63
64
K4
K5
K6
K4
K5
K6
Trip
Trip
Trip
Trip
Trip
X3
X2
X1
43 44
53 54
63 64
K4
K5
K6
Trip
Trip
Trip
X3
X2
X1
CSU
41