Function assignment of external terminal and control
Setting
Signal
Second function selection
3
RT
Pr. 270 = 1 ∗2
4
AU
Terminal 4 input selection
5
JOG
Jog operation selection
External thermal relay input ∗3
7
OH
15-speed selection (combination with three speeds RL, RM,
8
REX
RH)
10
X10
Inverter run enable signal (FR-HC, FR-CV connection)
12
X12
PU operation external interlock
14
X14
PID control valid terminal
15
BRI
Brake opening completion signal
PU-external operation switchover (turning on X16 selects
16
X16
external operation)
18
X18
V/F switchover (V/F control is exercised when X18 is on)
24
MRS
Output stop
25
STOP
Start self-holding selection
60
STF
Forward rotation (assigned to STF terminal (Pr. 178) only)
Reverse rotation command (assigned to STR terminal (Pr. 179)
61
STR
only)
62
RES
Inverter reset
PU/NET operation switchover (turning on X65 selects PU
65
X65
operation)
External/NET operation switchover (turning on X66 selects
66
X66
NET operation)
Command source switchover (turning on X67 makes Pr. 338
67
X67
and Pr. 339 commands valid)
9999
No function
∗1
When Pr. 59 Remote function selection = "1" or "2", the functions of the RL, RM and RH signals are changed as given in the table.
∗2
When Pr. 270 Stop-on contact control selection = "1", functions of RL and RT signals are changed as in the table.
∗3
The OH signal turns on when the relay contact "opens".
NOTE
Changing the terminal assignment using Pr.178 to Pr.184 (input terminal function selection) may affect the other functions.
Make setting after confirming the function of each terminal.
One function can be assigned to two or more terminals. In this case, the terminal inputs are ORed.
The priorities of the speed commands are in order of jog, multi-speed setting (RH, RM, RL, REX) and PID (X14).
When the X10 signal (FR-HC, FR-CV connection-inverter operation enable signal) is not set or when the PU operation
external interlock (X12) signal is not assigned with Pr.79 Operation mode selection set to "7", the MRS signal shares this
function.
Use common terminals to assign multi-speeds (7 speeds) and remote setting. They cannot be set individually.
(Common terminals are used since these functions are designed for speed setting and need not be set at the same
time.)
When V/F control is selected by V/F switchover (X18 signal), second function is also selected at the same time.
Control between V/F and advanced (general-purpose) magnetic flux can not be switched during operation. In case
control is switched between V/F and advanced (general-purpose) magnetic flux, only second function is selected.
Turning the AU signal on makes terminal 2 (voltage input) invalid.
(2) Response time of each signal
The response time of the X10 signal and MRS signal is within 2ms.
The response time of other signals is within 20ms.
132
Function
Stop-on contact selection 1
Related Parameters
Pr. 44 to Pr. 51
Pr. 270, Pr. 275, Pr. 276
Pr. 267
Pr. 15, Pr. 16
Pr. 9
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Pr. 30, Pr. 70
Pr. 79
Pr. 127 to Pr. 134
Pr. 278 to Pr. 283
Pr. 79, Pr. 340
Pr. 80, Pr. 81, Pr. 800
Pr. 17
Pr. 79, Pr. 340
Pr. 79, Pr. 340
Pr. 338, Pr. 339
Refer to
Page
134
125
168
97
109
95
122
183
234
127
190
76, 79, 82,
113
133
124
135
135
191
191
194