Main circuit terminal specifications
400V class
FR-E740-016 to 095
Jumper
N/- P/+
R/L1 S/L2 T/L3
PR
Power supply
NOTE
Make sure the power cables are connected to the R/L1, S/L2, T/L3. Never connect the power cable to the U, V, W of the
inverter. Doing so will damage the inverter. (Phase need not be matched.)
Connect the motor to U, V, W. Turning on the forward rotation switch (signal) at this time rotates the motor
counterclockwise when viewed from the load shaft.
16
Screw size (M4)
IM
Screw size
(M4)
Motor
FR-E740-120, 170
Screw size (M4)
Jumper
R/L1 S/L2 T/L3
N/-
P/+ PR
Power supply
Screw size
(M4)
IM
Motor