Mitsubishi Electric FR-E720-600 Instruction Manual page 311

Hide thumbs Also See for FR-E720-600:
Table of Contents

Advertisement

(4)
Main differences and compatibilities with the FR-E500 Series
Item
V/F control
Control method
General-purpose magnetic flux vector control
Torque boost (Pr. 0) initial value
FR-E520-1.5K to 7.5K: 6%
FR-E540-1.5K to 3.7K: 6%
FR-E540-5.5K, 7.5K: 4%
DC injection brake operation voltage (Pr. 12) initial value
FR-E520-0.4K to 7.5K: 6%
Frequency at 5V (10V) input (Pr. 38 )
Frequency at 20mA input frequency (Pr. 39 )
Second electronic thermal O/L relay (Pr. 48 )
Shortest acceleration/deceleration mode (Pr. 60 )
Reverse rotation from the inverter operation panel
Press
FM terminal function selection (Pr. 54) setting, AM
terminal function selection (Pr. 158) setting
0: Output frequency (initial value),
1: Output current,
2: Output voltage
Second applied motor
Pr. 71 = 100 to 123
Changed/cleared
Terminal 2 0 to 5V, 0 to 10V selection (Pr. 73 ) setting
functions
0: 0 to 5V (initial value),
1: 0 to 10V
Operation mode selection (Pr. 79 )
Initial value 1: PU operation mode
Setting 8: Operation mode switching by external signal
Setting general-purpose magnetic flux vector
Pr. 80 ≠ 9999
User group 1 (16), user group 2 (16)
(Pr. 160, Pr. 173 to Pr. 175 )
Input terminal function selection (Pr. 180 to Pr. 183 ) setting
5: MRS signal (output stop)
6: STOP signal (start self-holding selection)
Cooling fan operation selection (Pr. 244 ) initial setting
0: Cooling fan operates in power-on status.
Stop selection (Pr. 250 ) setting increments
1s
RS-485 communication control source from the PU connector
PU operation mode
Earth (ground) fault detection
400V class: Detects always
Inrush current limit circuit Provided for the 200V class 2.2K or more and 400V class
Fixed terminal block (can not be removed)
Control terminal block
(+ screw M2.5)
200V class: FM (pulse output)
Output signal
400V class: AM (analog output)
Operation panel
Removable operation panel (PA02)
PU
FR-PU04
for 400V class only
FR-E5NC : CC-Link communication
Plug-in option
FR-E5ND : DeviceNet communication
FR-E5NL : L
Installation size
0.1 to 7.5K are compatible in mounting dimensions
FR-E500
.
Dedicated plug-in option (installation is incompatible)
W
communication
ON
ORKS
FR-E700
V/F control
General-purpose magnetic flux vector control
Advanced magnetic flux vector control
Optimum excitation control
FR-E720-080 to 175: 4%
FR-E720-240, 330: 3%
FR-E740-040 to 095: 4%
FR-E740-120, 170: 3%
FR-E720-030 to 330: 4%
Parameter number change
(Pr. 125 Terminal 2 frequency setting gain frequency)
(Pr. 126 Terminal 4 frequency setting gain frequency)
(Pr. 51 Second electronic thermal O/L relay)
(Pr. 60 Energy saving control selection)
(Pr. 292 Automatic acceleration/deceleration)
After setting "1" in Pr. 40 RUN key rotation direction
selection , press
.
AM terminal function selection (Pr. 158) setting
1: Output frequency (initial value),
2: Output current,
3: Output voltage
Pr. 450 Second applied motor
Pr. 73 Analog input selection
0: 0 to 10V
1: 0 to 5V (initial value)
Initial value 0: External operation mode is selected at
power on
Setting 8: deleted (X16 signal is used instead)
Pr. 80 ≠ 9999, Pr. 81 ≠ 9999, Pr. 800 = 30
User group (16) only, setting methods were partially changed
(Pr. 160, Pr. 172, Pr. 173 )
Pr. 178 to Pr. 184 Input terminal function selection setting
5: JOG signal (jog operation selection)
6: None
24: MRS signal (output stop)
25: STOP signal (start self-holding selection)
1: Cooling fan on/off control valid
0.1s
Network operation mode (PU operatioin mode as FR-
E500 when Pr. 551 = 2)
400V class: Detects only at a start
Provided for the all capacity
Removable terminal block
(- screw M2 (M3 for terminal A, B, and C only)
AM (analog output) for all voltage class
Integrated operation panel (can not be removed)
FR-PU07
FR-PU04 (some functions, such as parameter copy, are
unavailable.)
FR-A7AX E kit : 16bit digital input
FR-A7AY E kit: Digital output, Extension analog output
FR-A7AR E kit: Relay output
FR-A7NC E kit : CC-Link communication
FR-A7ND E kit : DeviceNet communication
FR-A7NP E kit : PROFIBUS-DP communication
FR-A7NL E kit :L
W
communication
ON
ORKS
309

Advertisement

Table of Contents
loading

Table of Contents