Frequency setting by external terminals
(2) Multi-speed setting for 4 or more speeds (Pr. 24 to Pr. 27, Pr. 232 to Pr. 239)
Frequency from 4 speed to 15 speed can be set according to the combination of the RH, RM, RL and REX signals. Set the
running frequencies in Pr. 24 to Pr. 27, Pr. 232 to Pr. 239 (In the initial value setting, speed 4 to speed 15 are unavailable).
For the terminal used for REX signal input, set "8" in any of Pr. 178 to Pr. 184 (input terminal function selection) to assign the
function.
Speed 10
Speed 11
Speed 12
Speed 9
Speed 13
Speed 8
ON ON ON ON
RH
ON ON
RM
ON
ON
ON
RL
ON
ON
ON ON ON ON ON ON
REX
*1
∗1
When "9999" is set in Pr. 232 Multi-speed setting (speed 8), the frequency
changes to 0Hz when RH, RM and RL are turned off and REX is turned on.
REMARKS
The priorities of the frequency commands by the external signals are "jog operation > multi-speed operation > terminal 4 analog
input > terminal 2 analog input".
(Refer to page 171 for the frequency command by analog input)
Valid in the external operation mode or PU/external combined operation mode (Pr. 79 = "3" or "4").
Multi-speed parameters can also be set in the PU or external operation mode.
Pr. 24 to Pr. 27 and Pr. 232 to Pr. 239 settings have no priority between them.
When Pr. 59 Remote function selection ≠ "0", multi-speed setting is invalid as RH, RM and RL signals are remote setting signals.
NOTE
Changing the terminal assignment using Pr. 178 to Pr. 184 (input terminal function selection) may affect the other
functions. Make setting after confirming the function of each terminal.
Parameters referred to
Pr. 15 Jog frequency
Pr. 59 Remote function selection
Pr. 79 Operation mode selection
Pr. 178 to Pr. 184 (input terminal function selection)
96
Speed 14
Speed 15
Time
ON ON
ON
Refer to page 97
Refer to page 99
Refer to page 183
Forward rotation
Multi-speed
selection
Multi-speed operation connection example
Refer to page 131
Inverter
STF
REX
10
Frequency setting
RH
2
potentiometer
RM
5
RL
SD