ABB HiPerGuard MV UPS User Manual
ABB HiPerGuard MV UPS User Manual

ABB HiPerGuard MV UPS User Manual

Medium voltage ups
Hide thumbs Also See for HiPerGuard MV UPS:

Advertisement

MEDIUM VO LTAGE UPS
HiPerGuard MV UPS
User Manual
© Copyright 2023 ABB, All rights reserved.

Advertisement

Table of Contents
loading

Summary of Contents for ABB HiPerGuard MV UPS

  • Page 1 — MEDIUM VO LTAGE UPS HiPerGuard MV UPS User Manual © Copyright 2023 ABB, All rights reserved.
  • Page 2 T HE M A RKE T, AT 98 PE RC E NT – T R AN SL ATI NG TO A P OTE NT I A L CA RBO N EM ISS IO N RED U C TI ON O F 1 ,360 TO N S O VE R A T YP I CA L 1 5-YE A R L I FES PA N . — ABB's HiPerGuard MV UPS is an industry-first that provides a continuous and reliable power...
  • Page 3 – Graphical Display Module (GDM) – Control and adjustments This manual does not claim to cover all variations and details of the HiPerGuard MV UPS, nor to consider all eventualities that may arise during the operation of the product. Installation, commissioning, and maintenance of the product are covered in other documents, as listed in the following section.
  • Page 4 The personnel shall be qualified to prepare the installation site according to the site and equipment requirements and to perform the installation accordingly. Commissioning of the HiPerGuard must only be performed by qualified and certified ABB personnel. Electrical installation The personnel shall have a sound knowledge of the relevant electrical codes and specifications covering low and medium voltage equipment, be experienced with electrical wiring principles, and know the electrical symbols typically used in wiring diagrams.
  • Page 5 Intended use of equipment Those in charge of the HiPerGuard MV UPS shall ensure that the product is only used as specified in the contractual documents, operated under the conditions stipulated in the technical specifications and on the rating plate of the product, and serviced in the intervals as specified by ABB.
  • Page 6 Abbreviations & Terms The following table lists terms and abbreviations users should be familiar with when using this manual. Some of the terms and abbreviations used in the manual are unique to ABB and might differ from the common use.
  • Page 7 PCS120 ABB power conditioning products. Power Conversion Unit. The PCU consists of the LV enclosures of the HiPerGuard MV UPS unit. Platform Enclosure 120. PE120 is the enclosure that contains several PCS120 PE120-N modules. The product has three enclosures designated as PE120-1, PE120-2 &...
  • Page 8 Uninterruptible Power Supply Unit. Refers to a single HiPerGuard MV UPS UPSU machine. Impedance Isolated Static Converter. ZISC refers to the architecture of the ZISC HiPerGuard MV UPS where the static power converters of the MV UPS are isolated from the grid via an impedance. https://new.abb.com/ups/ 8/104...
  • Page 9 The following registrations and trademarks are used in this manual: Abbreviation/Term Meaning Modbus® Registered trademark of Schneider Electric USA, Inc HiPerGuard® Registered trademark of ABB New Zealand Ltd. — Related documentation The following documents are available for further information: Document title Document type...
  • Page 10 HiPerGuard. While every care has been taken to ensure the completeness and accuracy of this manual, ABB assumes no responsibility or liability for any losses or damages resulting from the use of the information contained in this document.
  • Page 11: Table Of Contents

    5.2. Load output ..............................45 5.3. Energy Storage ............................45 5.4. MV Switchgear ............................46 5.5. Environmental conditions ........................46 5.6. Interface ............................... 47 5.7. Dimensional data ............................48 External power and control connections ..................... 49 6.1. Overview of external connections ......................49 https://new.abb.com/ups/ 11/104...
  • Page 12 8.2. System Start ..............................90 8.3. System Bypass ............................95 8.4. Independent mode ............................96 8.5. Resynchronize mode ..........................98 8.6. System EPO (Emergency Power OFF) ....................98 8.7. Hard fault ..............................99 8.8. Energy storage depleted ........................100 Maintenance Schedule ..........................101 9.1. Overview..............................101 https://new.abb.com/ups/ 12/104...
  • Page 13: Safety

    S A FET Y Safety ‫ﺧطر‬ ‫ﻛﮭرﺑﺎﺋﻲ‬ ‫ﺟﮭد‬ ‫ﺗﺣذﯾر‬ ‫اﻟﺗﺷﻐﯾل‬ ‫ﺗﻌﻠﯾﻣﺎت‬ ‫راﺟﻊ‬ ‫اﻟﺟﮭﺎز‬ ‫ھذا‬ ‫ﻓﻲ‬ ‫اﻟﻌﻣل‬ ‫ﻗﺑل‬ ‫ﺑﺗﺄﻣﯾﻧﮭﺎ‬ ‫وﻗم‬ ‫اﻟﻛﮭرﺑﺎء‬ ‫اﻓﺻل‬ ‫اﻟﻛﮭرﺑﺎﺋﯾﺔ‬ ‫اﻟﺗﻘﻧﯾﺔ‬ ‫ﺑﻣﺟﺎل‬ ‫دراﯾﺔ‬ ‫ﻋﻠﻰ‬ ‫ﺷﺧص‬ ‫ﺧﻼل‬ ‫ﻣن‬ ‫إﻻ‬ ‫اﻟﺗرﻛﯾب‬ ‫ﻋدم‬ ‫ﯾﺟب‬ ‫ﺗﻧﺑﯾﮫ‬ Предупреждение: Опасно напрежение! Вижте инструкциите за работа. Изключете...
  • Page 14 S A FET Y Avertissement: Tension dangereuse! Consultez les consignes d’utilisation. Débranchez et verrouillez l’alimentation électrique avant d’entreprendre des travaux sur cet appareil. Attention! L’installation doit être effectuée uniquement par une personne ayant une expertise en électrotechnique. Upozorenje: Opasan napon! Pogledajte upute za uporabu.
  • Page 15 S A FET Y Aviso: Tensão perigosa! Consulte as instruções de operação. Desconecte e desligue a energia elétrica antes de trabalhar nesse dispositivo. Atenção! A instalação deve ser feita apenas por uma pessoa com especialidade eletrotécnica. Avertisment: Tensiune electrică periculoasă! Consultați instrucțiunile de utilizare.
  • Page 16: Safety Notices

    Stored charge is present after the device is switched off. When the HiPerGuard is powered down, lethal voltages will remain in the energy storage elements and the complete HiPerGuard MV UPS should be considered live. To remove this hazard, energy storage will need to be isolated and locked off, and filter capacitors discharged.
  • Page 17 S A FET Y Symbol/sign Meaning D A N G E R – Arc flash Arc flash is a dangerous phenomenon associated with operation at medium voltages. It may be caused by switchgear failure, insulation breakdown or foreign object intrusion. It may result in severe burns, severe eye injury, blindness or death. To minimize the risk, keep all doors closed and covers in place while operating the equipment.
  • Page 18: General Safety Information

    S A FET Y 1.2. General safety information 1.2.1. Operator duties The scope of work for an operator of the HiPerGuard is to control and monitor the HiPerGuard from the GDM, remote start/stop controls, or from the web page. An operator is not normally authorized to undertake any maintenance, service, or repair work.
  • Page 19: Cyber Security Legal Disclaimer

    2.1. Deployment guidelines The recommended Cyber Security deployment for the HiPerGuard MV UPS is for it to be only used in a trusted network with restricted access. The user is responsible for creating a defense-in-depth protection by allocating firewall solutions to each network.
  • Page 20: Product Description

    Based on the ZISC (Impedance Isolated Static Converter) architecture, the HiPerGuard MV UPS uses a special coupling reactor combined with PEBB120 inverter modules to interface from the utility to the load.
  • Page 21: Operating Principle

    The resulting performance is continuous clean power in accordance with IEC62040-3 VI SS 111. The efficiency is greater than 98% for the load spectrum from 50% up to rated full load. When operating on the Power Conditioning mode, the HiPerGuard MV UPS can supply high fault currents for downstream protection.
  • Page 22 3.2.2. Independent mode If the utility power is no longer available or in a prolonged sag event, the HiPerGuard MV UPS opens the input circuit breaker and transfers the load to the energy storage, operating now in Independent mode. The energy storage allows ride-through time for either the utility power to be restored or for the time necessary for an alternative energy source to be activated, such as a generator, for example.
  • Page 23 P RO DU C T D ES C R IP T I ON The input breaker management graph is split into two regions. The first part, a slow filter curve down to 50% input voltage, is designed for thermal management of the MV UPS and protection coordination. It allows the MV UPS to keep the input circuit breaker closed for typically 1 second at 50%.
  • Page 24 P RO DU C T D ES C R IP T I ON 3.2.5. Transition from Independent to Power Conditioning mode (upstream generator adaptive walk-in) Frequently diesel or gas generators are connected to the MV UPS input as secondary power supplies in case of extended duration power outages.
  • Page 25 P RO DU C T D ES C R IP T I ON The process is the same for a single or several generators connected to the MV UPS input busbar. The minimum walk-in time is defined by the capacity of the generator (or generators) to support the load based on the frequency error.
  • Page 26 3.2.6. Automatic bypass operation In case of an expected or unexpected HiPerGuard MV UPS shutdown, the load current is transferred to the automatic bypass breaker. The MV switchgear acts as the primary system bypass, and its operation is fully controlled by the MV UPS, while the MV UPS control switch located on the switchgear is in “UPS Control”...
  • Page 27 MV UPS autonomy support. Figure 3.8:Battery SOC Under all modes, the HiPerGuard MV UPS maintains the output voltage at its nominal voltage level. Voltage control and Demand Response are considered independent functions as one does not affect the other.
  • Page 28 If the Power Exchanger function is deactivated, the grid will support the entire load power. The HiPerGuard MV UPS will manage the battery and charge it to 100% SOC. HI PE RG UA RD M V UP S U S E R M A N UA L...
  • Page 29 Figure 3.11: MV UPS power flow – Demand to inject power from the battery; P < P Load If the demanded power P exceeds the load power, then the HiPerGuard MV UPS shall limit the P to be equal to P <=P...
  • Page 30 P RO DU C T D ES C R IP T I ON 3.2.7.3.3. Demand to absorb power into the battery If the DRC requests the MV UPS to absorb power into the battery, the system will charge the battery while ensuring that the output voltage stays at its nominal level.
  • Page 31 P RO DU C T D ES C R IP T I ON Figure 3.13: HiPerGuard MV UPS Auxiliary Power Supply HI PE RG UA RD M V UP S U S E R M A N UA L 31/103...
  • Page 32: Major Mv Ups Components

    P RO DU C T D ES C R IP T I ON 3.3. Major MV UPS components This section introduces the main components of the HiPerGuard MV UPS. Figure 3.14: HiPerGuard MV UPS 2.5 MVA product overview Platform Enclosure (PE120-1) –...
  • Page 33 P RO DU C T D ES C R IP T I ON Figure 3.15: HiPerGuard MV UPS major components – front side Figure 3.16: HiPerGuard MV UPS major components – rear side HI PE RG UA RD M V UP S U S E R M A N UA L...
  • Page 34 3.3.1.1. PCS120 Power Electronic Building Blocks The HiPerGuard MV UPS has eighteen PEBBs. The Power Electronic Building Blocks are high efficiency three-level bi-directional power electronics IGBT-based converters. Each PEBB is rated at 250 kVA and includes a sine filter. The PEBBs are plug-in modules with automatic smart firmware management and controlled via 2 x fiber optic cables and powered on by 24 Vdc connection.
  • Page 35 3.3.1.2. Graphical Display Module (GDM) The GDM is located in the PE120-1 enclosure. This user interface of the HiPerGuard MV UPS is connected to the system controller. Through the GDM, it is possible to operate the MV UPS, read/edit its parameters, reset alarms and faults, and access power-quality events data.
  • Page 36 P RO DU C T D ES C R IP T I ON The APS enclosure is fan cooled with N+1 fan redundancy. The enclosure has gland plates that al-low for both top and bottom wiring entry. Figure 3.22: Auxiliary power supply enclosures (APS) 3.3.2.1.
  • Page 37 P RO DU C T D ES C R IP T I ON 3.3.3. Medium Voltage Magnetics enclosure (MVM) This is the medium voltage section of the MV UPS that includes the coupling transformer and the line reactor. The coupling transformer connects the low voltage power converters to the medium voltage network.
  • Page 38: Cooling System

    The LV enclosures and the MVM enclosure are equipped with fan units. The fan units’ intake cooling air to the HiPerGuard MV UPS major components with the objective of transfer the internally generated heat to the outside of the enclosures.
  • Page 39 P RO DU C T D ES C R IP T I ON 3.4.1. PE120 Enclosure air flow diagram The enclosure airflow is managed as shown in Figure 3.28, where the air gets drawn from the Enclosure front through the PEBBs fans and routed to the back and then upwards to the top exhaust. Figure 3.28: PE120 Enclosure air flow diagram HI PE RG UA RD M V UP S U S E R M A N UA L 39/103...
  • Page 40: Model Definition

    Product type code The product order code defines the characteristics and features of the HiPerGuard MV UPS. The order code is unique for each model of HiPerGuard MV UPS and specifies all the parameters needed to order the product. Figure 4.1 outlines the structure of the order code.
  • Page 41: Medium Voltage Cable Entry

    “1” in their code, while single units are identified by the number “0”. For example, if the total load is 9 MVA, the system shall be composed of 4 HiPerGuard MV UPS units with the number “1”...
  • Page 42: 4.10. Installation

    “back-to-back” arrangement. 4.12. Power Exchanger interface The HiPerGuard MV UPS can provide a Power Exchanger (PE) interface for an external demand response controller (DRC). The demand response interface allows the customer to manage changes in supply/demand for electrical power.
  • Page 43: Options (Plus Codes)

    M O D E L D E F IN I TI ON 4.15. Options (Plus Codes) The following options are available with HiPerGuard MV UPS. Plus code Option description Note Cable Spacer Available only for the MVM. The cable spacer is only needed if the customer has top cable entry to the MVM and also has cables with low flexibility.
  • Page 44: Technical Specifications

    96% for 25% to 50% loading conditions Dynamic output In line with IEC62040-3 VI SS 111 performance Architecture ZISC enabled line interactive Table 5.1: HiPerGuard MV UPS general data 5.1. Utility input Input Voltage tolerance ±10 % From nominal voltage...
  • Page 45: Load Output

    Full linear load, under nominal conditions, operating on power Voltage distortion THDv < 2.5% conditioning mode Table 5.3: HiPerGuard MV UPS output specifications 5.3. Energy Storage Energy Storage Type Li-Ion batteries (not in the scope of UPS supplier)
  • Page 46: Mv Switchgear

    MV Switchgear MV Switchgear Voltage Class 7.2 kV IEC / 12 kV IEC / 15 kV ANSI / 24 kV IEC MV Switchgear supplier ABB qualified (supplied separately) Table 5.5: MV switchgear specifications 5.5. Environmental conditions Environmental Excluding energy storage Daily and yearly max.
  • Page 47: Interface

    (changeover relay Hardwired interface contacts) Enable switch (Bi-stable physical switch to allow machine start) Table 5.7: HiPerGuard MV UPS interface specifications HI PE RG UA RD M V UP S U S E R M A N UA L 47/103...
  • Page 48: Dimensional Data

    AC Input / AC Output dependent DC Input Top / Bottom Connection Type Cable Table 5.8: HiPerGuard MV UPS dimensional data HI PE RG UA RD M V UP S U S E R M A N UA L 48/103...
  • Page 49: External Power And Control Connections

    6.1. Overview of external connections The HiPerGuard MV UPS has various control and power connections terminated at different locations. Medium voltage AC power connections are made at the MVM enclosure. Protective earth and DC power connections are made at the DCT enclosure.
  • Page 50: Energy Storage Connections To Dct Enclosure

    GDM. When the ENABLE switch circuit is de-asserted, i.e., circuit is opened, it inhibits start-up of the HiPerGuard MV UPS. If the UPS is already started and running in either PCM or IM when the ENABLE switch circuit is opened, the UPS shall transfer the load to the grid by closure of bypass and opening of input and output switches, and simultaneously stopping the power converters.
  • Page 51 EX TE R NA L P OW E R A ND CO N T RO L CO N NE C T IO NS 6.4.2. External auxiliary 3-phase power supply input An external power supply is required for system start-up. This is not needed once the system is running. The requirements are summarized in Table 6.1.
  • Page 52 Table 6.2: Status feedback relay functions and wiring 6.4.4. Digital inputs The HiPerGuard MV UPS has multiple digital inputs available for external control. Emergency Power Off (EPO), start, stop, and reset functions are accessible through terminal blocks located in the APS enclosure.
  • Page 53 The stop input is active low level triggered, which means that a transition from 24 Vdc to 0 V will command the HiPerGuard MV UPS to stop. If the control via DI is not required, the terminals X11:5 and X11:6 on the APS enclosure shall be linked out. The stop input is a "maintained" operator switching type.
  • Page 54 6.4.5. Energy Storage Interface The HiPerGuard MV UPS shall connect to an energy storage Battery Management System (BMS) either via a dedicated hardwired remote I/O interface or indirectly using an external SCADA/PLC MODBUS client. This interface selection is performed using a source-select parameter.
  • Page 55 Please refer to latest revision of schematic 2UCD000500E356 HiPerGuard MV UPS BATT_DR_GEN EXT IO IF for interconnection details. HI PE RG UA RD M V UP S U S E R M A N UA L...
  • Page 56 EX TE R NA L P OW E R A ND CO N T RO L CO N NE C T IO NS Figure 6.7: Energy Storage enclosure controller connections HI PE RG UA RD M V UP S U S E R M A N UA L 56/103...
  • Page 57 6.4.6.1. Power Exchanger Interface It is possible to configure the HiPerGuard MV UPS to provide grid support services to aid the utility grid in the supply of power if ever the grid demand temporarily exceeds grid supply. This requires the connection to a third party “Demand Response Controller”...
  • Page 58 EX TE R NA L P OW E R A ND CO N T RO L CO N NE C T IO NS Figure 6.8: HiPerGuard MV UPS Power Exchanger and Generator Interface connections 6.4.7. Generator Interface In some installations with local generator(s) providing back-up in the event of loss of mains power supply, an event such as a step load change can affect the frequency stability of the generator(s).
  • Page 59 EX TE R NA L P OW E R A ND CO N T RO L CO N NE C T IO NS 6.4.8. Internal MODBUS TCP network interface The Ethernet communications cables connected to the energy storage enclosure (Section 6.4.5), Power Exchanger Interface (6.4.6.1), and generator interface (6.4.6.2) are connected to the Ethernet switch A1, located in the UPS APS enclosure.
  • Page 60: Communication Between Mv Ups And Mv Switchgear

    EX TE R NA L P OW E R A ND CO N T RO L CO N NE C T IO NS 6.5. Communication between MV UPS and MV Switchgear There is a high-speed optical communication link between the MV UPS’s system controller and the switchgear.
  • Page 61: Modbus Tcp/Web Interfaces

    120 m. A pair of 120 m long HCS fiber optic cables, ready for installation is issued by ABB. The connectors are located on the bottom of the APS cabinet, as shown in Figure 6.11.
  • Page 62: Communication Between Mv Ups Units In Parallel Configuration

    Figure 6.13: Parallel machine communications network Figure 6.13 shows 10 HiPerGuard MV UPS units connected in parallel. Note that two network switches are required (not included on MV UPS scope of supply), each with enough Ethernet ports to support the number of units in parallel.
  • Page 63: User Interface

    7.1. Graphic Display Module (GDM) The primary user interface for configuration of the HiPerGuard MV UPS is via the Graphical Display Module (GDM) which is mounted on the door of the PE120-1 enclosure. It allows local control of the HiPerGuard MV UPS, shows the UPS block status, and provides access to the operating parameters and event history.
  • Page 64 U S E R I NT E R FA CE Figure 7.1: GDM – UPS block stop - confirmation screen Figure 7.2: GDM – UPS Block – Start/Stop, Reset buttons Figure 7.3: UPS BLOCK: RESET Confirmation Window HI PE RG UA RD M V UP S U S E R M A N UA L 64/103...
  • Page 65 U S E R I NT E R FA CE Below the status bar, there is a symbol that indicates the MV UPS health with event code that displays the highest priority. (For example, an unlikely block trip has a higher display priority than a block warning).
  • Page 66 U S E R I NT E R FA CE Icon Description Information Service Settings User Login Table 7.1: GDM dashboard icons 7.1.2. General Overview Figure 7.6 shows the distribution of information across the GDM pages. The next sections will provide a detailed description of each page.
  • Page 67 U S E R I NT E R FA CE Figure 7.6: Pages map HI PE RG UA RD M V UP S U S E R M A N UA L 67/103...
  • Page 68 U S E R I NT E R FA CE 7.1.3. GDM main screen The GDM home screen is the “Block Main Dashboard”, where it shows block status and real-time measurements. This page has three main columns: Input – Shows input three-phase voltage (kV), frequency (Hz), active power (kW), reactive power (kVAR) and apparent power (kVA) measurements on the left.
  • Page 69 U S E R I NT E R FA CE The power flow in the MV UPS block is categorized into four block states System states Bypassed Starting/ Power Independent Stopping Conditioning Mode Mode Figure 7.8: Power flow SLD categories on GDM 7.1.4.
  • Page 70 U S E R I NT E R FA CE Figure 7.9: GDM- STOP confirmation Dialogue box Figure 7.10: STOP confirmation for entire system Figure 7.11: STOP confirmation for single block HI PE RG UA RD M V UP S U S E R M A N UA L 70/103...
  • Page 71 U S E R I NT E R FA CE The System view shows all blocks connected in hard parallel configuration and their mode of operation as illustrated in Figure 7.12. Figure 7.12: MV UPS system view page A “Reset” button is available on the bottom right side of the screen below the Start/Stop button. When activated, this button will rest a single block or all UPSs simultaneously.
  • Page 72 U S E R I NT E R FA CE Figure 7.14: RESET confirmation for entire system Figure 7.15: RESET confirmation for single Block 7.1.5. Precharge This screen shows whether DC bus Precharge conditions are achieved or not and if the converter DC bus voltage and energy storage DC bus voltage are the same or not.
  • Page 73 U S E R I NT E R FA CE The symbols on the pre-charge page represent the following: DC bus Voltage: – Displayed as numeric value and in bar chart. Charger: – Health: It is possible to identify the charger health depending on the fill color. Red indicates fault, yellow shows Warning and No Fill color means the charger is healthy.
  • Page 74 U S E R I NT E R FA CE 7.1.6. Active Events This screen shows a list of the block messages for currently active events like warnings and faults. When clicking on an active event on the left side of the window, a description of the warning of fault is displayed on the event details field.
  • Page 75 U S E R I NT E R FA CE 7.1.6.1. List of Warnings Event Description The UPS has been placed in Test Mode while it is W5.4 UPS in Test Mode while Run running. W5.12 UPS Topology not selected The topology of the UPS system has not been selected.
  • Page 76 U S E R I NT E R FA CE Event Description W5.97 Input voltage outside nominal range The UPS mains input voltage is outside its nominal range. Input voltage outside nominal in Test The measured input voltage is outside its normal W5.98 mode range while the UPS is in CSI Test Mode or Island...
  • Page 77 U S E R I NT E R FA CE Event Description W5.146 S racked out Output Switch circuit breaker is detected as being racked out from its cubicle. W5.149 S relay warning Output switch circuit breaker relay warning. Automatic Bypass switch circuit breaker reports as W5.155 S unexpectedly ready to transition ready to transition before software thinks it should.
  • Page 78 U S E R I NT E R FA CE Event Description W5.211 Demand Response Power Controller There is a communication problem between the communications link invalid Demand Response Power Controller and the MV UPS. W5.213 Demand Response Power Controller The Demand Response Controller is LIMITING STATE limiting charging OF CHARGE of the Energy Storage.
  • Page 79 U S E R I NT E R FA CE Event Description F5.86 UC to ML 1 link failure The UC’s CPU has indicated a failure in communications handshake between UC and ML link 1. F5.93 PCS-120 Group Faulted PCS-120 modules have reported a group error. The number of PCS-120 modules available is insufficient to allow system to run.
  • Page 80 U S E R I NT E R FA CE Event Description F5.171 Output voltage too low timed The RMS value of output line voltage has fallen below the low voltage threshold value for more than a preset time. F5.173 Programmed trip The system has been deliberately tripped, as part of a specific test routine.
  • Page 81 U S E R I NT E R FA CE Figure 7.18: Event Log page Icon Description/Function Indicates the number of active events (can be seen from any page) Indicates a fault Indicates a warning Indicates a power quality event Move to the next event log page Return to the previous event log page Return to the first page (latest event)
  • Page 82 U S E R I NT E R FA CE 7.1.8. Power Quality Events This page lists the power quality events detected since the MV UPS was first started. Note that the log has a capacity of up to 10,000 events. The oldest events appear at the bottom of the log. If the events fill to its capacity, the oldest event in the log will be over-written with the latest event.
  • Page 83 7.1.9. Energy storage test mode The HiPerGuard MV UPS typically uses Lithium-Ion energy storage that has associated Battery management System (BMS) which monitor battery state-of-health. The MV UPS has incorporated an energy storage test mode which when used in conjunction with the BMS facilitates the operator to make repeatable discharge tests for battery capacity trending and evaluation.
  • Page 84 U S E R I NT E R FA CE 7.1.11. Information This page includes the information such as License information, Service log, Firmware versions and System State. Figure 7.20: Product Information page 7.1.12. Service This page is dedicated for service trained authorized personnel that need special access requirements. The settings page includes several sub-pages such as test and calibration pages.
  • Page 85 U S E R I NT E R FA CE 7.1.13.1. List of Parameters Group Subgroup Parameter Description Access General Customer Name Read/Write General Customer Tag Name Read/Write General Customer Identifier Read/Write General Site Name Read only General Product Name Read only General Model Name...
  • Page 86 Test Setup Read/Write Table 7.8: List of Parameters 7.1.14. User Login page The HiPerGuard MV UPS has four levels of user roles available from the touch screen: – Any User (default) – Operator – Service – Factory To log in, access the pin code entry screen from the main dashboard Login icon.
  • Page 87: Web Interface

    A web version of the HiPerGuard GDM is also accessible from the Local Area Network. The web interface can be accessed from any device with a web browser by entering the HiPerGuard MV UPS's IP address into the address bar. The IP Address can be obtained from the right-hand status bar on the GDM.
  • Page 88: Operation

    8.1. Machine State Flow diagram While the HiPerGuard MV UPS system is operational, it has two basic modes of operation - Power conditioning mode (PCM) and Independent mode (IM). This section explains the HiPerGuard MV UPS machine different states transitioning between modes of operation and the logic driving the control of transitioning from one state to another.
  • Page 89 When a power quality event is detected, and the grid voltage is out of threshold, the HiPerGuard MV UPS(s) transit(s) to “PCM_Active state”: – The HiPerGuard MV UPS(s) will attempt to ride through the event if it is a shallow surge or sag event. – If during the event, the grid voltage goes outside the S...
  • Page 90: System Start

    – When synchronization has been achieved, the HiPerGuard MV UPS(s) command(s) circuit breaker(s) Sin to close, and transits to “PCM_Normal state”. If a power quality event occurs while HiPerGuard MV UPS(s) is (are) in “Resynchronizing state”, then the MV UPS(s) will transit back to “Island state”.
  • Page 91 O P E R AT I O N Figure 8.2: MV UPS system in bypass and isolated Figure 8.3: MV UPS system (hard parallel) in bypass and isolated HI PE RG UA RD M V UP S U S E R M A N UA L 91/103...
  • Page 92 O P E R AT I O N Step User Action System Response User selects “Precharge” screen on GDM and presses Charger “Enable” button MV UPS auxiliary charger shall charge up the converter DC bus to a preset threshold. The User shall confirm that the battery voltage measured at the battery and the DC bus voltage as displayed on GDM screen are reasonably matched.
  • Page 93 O P E R AT I O N Figure 8.5: System (hard parallel) after “Precharge” process of the DC bus is complete 8.2.2. System start Once sufficient MV UPS blocks are precharged, the MV UPS system is now ready to start and in bypass. In that case, the input voltage must be within nominal conditions, and all switches are under the control of the MV UPS (with springs charged), with input and output switches open.
  • Page 94 O P E R AT I O N Step User Action System Response User commands “START SYSTEM” MV UPS block performs a self-check MV UPS block checks if all its precharge conditions are met The MV UPS(s) synchronize(s) with utility voltage in magnitude, frequency and phase angle, then it closes S and then S...
  • Page 95: System Bypass

    O P E R AT I O N Figure 8.7: MV UPS (hard parallel) operating in Power Conditioning Mode 8.3. System Bypass The system can be bypassed from the GDM, Modbus TCP or digital I/O. If the System Stop button is pushed on the GDM and the MV UPS is in Independent mode or the utility voltage is not within acceptable limits, the system will ask the operator to confirm or abort the request.
  • Page 96: Independent Mode

    O P E R AT I O N Step User Action System Response Press “Stop” If the MV UPS system is in Independent mode or the utility voltage is not within acceptable limits, the system will ask the operator to confirm to abort the discharge and initiate system stop Commands to Close S...
  • Page 97 O P E R AT I O N Figure 8.8: MV UPS operating in Independent Mode (IM) Figure 8.9: MV UPS (hard parallel) operating in Independent Mode (IM) HI PE RG UA RD M V UP S U S E R M A N UA L 97/103...
  • Page 98: Resynchronize Mode

    O P E R AT I O N 8.5. Resynchronize mode While the MV UPS(s) is (are) disconnected from the input and supplying the load, it monitors the input voltage for the return of the grid supply or a backup generator. When the voltage reappears at the input, the MV UPS system waits for 1-2 seconds to make sure that the supply is stable and reliable enough for reconnection.
  • Page 99: Hard Fault

    O P E R AT I O N Step User Action System Response Open all DC breakers at the DC energy source if configured to do so Table 8.6: MV UPS Emergency Power Off steps 8.7. Hard fault Hard faults are extremely rare situations where multiple failures occur at the same time, and the system is not capable of holding the voltage any longer.
  • Page 100: Energy Storage Depleted

    O P E R AT I O N Step User Action System Response When S is closed or S close request time- out period is elapsed then MV UPS opens S and S . MV UPS stops the PEBBs and reverts to bypass mode Table 8.8: System reaction to fault while in IM 8.8.
  • Page 101: Maintenance Schedule

    The recommended intervals for maintenance and component replacement are based on the normal operating conditions of the HiPerGuard MV UPS. The HiPerGuard MV UPS should be checked at least annually by qualified personnel whose recommendations should be followed. Depending on the actual conditions of the MV UPS, maintenance work can be carried out before or after the recommended interval.
  • Page 102 M AI N TE N A N C E S C H ED U LE 102/103...
  • Page 103 We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB Ltd. does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.

Table of Contents