LUNA2000-200KTL-H0 Smart Power Control System
User Manual
No.
Category
33
34
35
36
Voltage rise
suppression P-U
curve
37
38
Issue 05 (2022-06-30)
Parameter
Description
VRT active
Specifies the recovery rate
power recovery
when the active current
gradient
recovers to the value at the
moment before FRT.
Zero current due
Specifies whether to enable
to power grid
the Zero current due to
fault
power grid fault function.
Zero current due
This parameter can only be
to power grid
set for the VDE4120.
fault
Voltage rise
The standards of certain
suppression
countries and regions require
that when the output voltage
exceeds a certain value, the
device must suppress a rise in
voltage by outputting reactive
power and reducing active
power.
Voltage rise
The standards of certain
suppression
countries and regions require
reactive
the device to generate a
adjustment
certain amount of reactive
point (%)
power when the output
voltage exceeds a certain
value.
Voltage rise
The standards of certain
suppression
countries and regions require
active derating
the active power of the device
point (%)
to be derated by a certain
slope when the output
voltage exceeds a certain
value.
Copyright © Huawei Technologies Co., Ltd.
8 Device Commissioning
Remarks
-
-
-
-
● This parameter is
displayed when
Voltage rise
suppression is set
to Enable.
● The value of
Voltage rise
suppression
active derating
point must be
greater than that
of Voltage rise
suppression
reactive
adjustment
point.
-
65