LUNA2000-200KTL-H0 Smart Power Control System
User Manual
Check Item
System running
status
Cable
connections
Grounding
reliability
Removing the Air Inlet Baffle
Figure 9-1 Removing the baffle
After cleaning is complete, reinstall the air inlet baffle. Tighten the screws to a
torque of 1.2 N·m.
Issue 05 (2022-06-30)
Check Method
● Check that the Smart PCS is not
● Check that the Smart PCS
● Check that the parameters are
● Check that cables are secured.
● Check that cables are intact,
● Check that the idle COM, USB,
Check that ground cables are
securely connected.
NO TICE
Copyright © Huawei Technologies Co., Ltd.
damaged or deformed.
operates with no abnormal
sounds.
set correctly.
and ensure that any parts in
contact with metallic surfaces
are not scratched.
and FE ports are protected by
waterproof caps.
9 Device Maintenance
Maintenance
Interval
Once every 6 months
The first inspection
must be performed 6
months after the
initial commissioning.
Subsequent
inspections can be
performed every 6 to
12 months.
The first inspection
must be performed 6
months after the
initial commissioning.
Subsequent
inspections can be
performed every 6 to
12 months.
73