Alternative Power Cable Types; Power Cable Types For Limited Use; Not Allowed Power Cable Types - ABB ACS880-77CC Hardware Manual

Wind turbine converters
Table of Contents

Advertisement

DC resistor cables
Converter type
Cable type
ACS880-77CC-
6880A/5500A-7
EPR

Alternative power cable types

The power cable types that you can use with the converter are shown below.
PE
PE
PE

Power cable types for limited use

PE

Not allowed power cable types

PVC
EMT
PE
Conductor
type
Copper
Symmetrical shielded cable with three phase conductors and a concentric PE
conductor as shield. The shield must meet the requirements of IEC 61800-5-1.
Check with local / state / country electrical codes for allowance.
Symmetrical shielded cable with three phase conductors and a concentric PE
conductor as shield. A separate PE conductor is required if the shield does not
meet the requirements of IEC 61800-5-1.
Symmetrical shielded cable with three phase conductors and symmetrically con-
structed PE conductor, and a shield. The PE conductor must meet the requirements
of IEC 61800-5-1.
A four-conductor system (three phase conductors and a protective conductor on
a cable tray) is not recommended for cabling.
A four-conductor system (three phase conductors and a PE conductor in a PVC
conduit)
Corrugated cable with three phase conductors and a protective conductor or cable
in EMT conduit
A well-shielded (Al/Cu shield) four-conductor system (three phase conductors and
a PE conductor or four conductors)
Symmetrical shielded cable with individual shields for each phase conductor is not
allowed on any cable size for grid and generator cabling.
Planning the electrical installation 53
Number of conductor pairs per DC chopper module
70 kcmil
2×1