HP P2000 Reference Manual page 17

Msa system event descriptions
Hide thumbs Also See for P2000:

Advertisement

163
Warning
The host WWNs (node and port) previously presented by the partner controller module, which is currently
offline, are unknown.
This event has two possible causes:
The online controller module reporting the event was replaced or moved while the system was powered
off.
The online controller module had its flash configuration (where previously used WWNs are stored)
cleared.
The online controller module recovers from this situation by generating a WWN based on its own serial
number for the other controller module.
Recommended actions
If the controller was replaced or someone reprogrammed its FRU ID data, verify the WWN information
for the other controller module on all hosts that access it.
166
Warning
The RAID metadata level of the two controllers does not match. Usually, the controller at the higher
firmware level can read metadata written by a controller at a lower firmware level. The reverse is typically
not true. Therefore, if the controller at the higher firmware level failed, the surviving controller at the lower
firmware level cannot read the metadata on disks that have failed over.
Recommended actions
If this occurs after a firmware update, it indicates that the metadata format changed, which is rare.
Update the controller with the lower firmware level to match the firmware level on the other controller.
167
Warning
A diagnostic test at controller bootup detected an abnormal operation, which might require a power cycle
to correct.
Recommended actions
See
Resources for diagnosing and resolving problems
168
Error
The indicated SES alert condition was detected in the indicated enclosure. This event is logged as Error
when one of the power supplies in an enclosure has no power supplied to it or when a hardware failure is
detected.
Recommended actions
Most voltage and temperature errors and warnings relate to the power supply module; see
page 44. If there is no problem with the power source, the indicated FRU has probably failed and
should be replaced.
When the problem is fixed, event 169 is logged.
Warning
The indicated SES alert condition was detected in the indicated enclosure.
Recommended actions
Most voltage and temperature errors and warnings relate to the power supply module; see
page 44.
When the problem is resolved, event 169 is logged.
Info.
The indicated SES alert condition was detected in the indicated enclosure.
Recommended actions
Most voltage and temperature errors and warnings relate to the power supply module; see
page 44.
on page 3.
HP P2000 G3 MSA System Event Descriptions Reference Guide