4−46

Multistage-position switch (1)~(3)

When
"66
settings from multistage positions 0 to 7.
Use multistage position settings 0 to 7
position settings are assigned to terminals, multistage position 0 (P060) is assumed.
You can specify a delay to be applied at multistage position setting input, until the
relevant terminal input is determined. Use this specification to prevent the application
of fluctuating terminal input before it is determined.
You can adjust the determination time with the multistage speed/position
determination time setting (C169). The input data is finally determined when the
terminal input becomes stable after the delay set as C169. (Note that a long
determination time deteriorates the input terminal response.)
Determination time (C169)=0
Position
command
CP1
CP2
CP3
Option
Terminal
Code
Symbol
CP1~CP3
66~68
Valid for inputs:
Required settings
Notes:
(CP1)" to
"68
(CP3)" are assigned to input terminals, you can select position
Position setting
Multistage position 0
Multistage position 1
Multistage position 2
Multistage position 3
Multistage position 4
Multistage position 5
Multistage position 6
Multistage position 7
3
1
Function Name
Multistage-position switch
(1)~(3)
C001~C007
P060~P067
(P060
to P067) for the position settings. If no
Parameter
CP3
0
P060
0
P061
0
P062
0
P063
1
P064
1
P065
1
P066
1
P067
7
Determination time
(C169) specified
ON
ON
ON
Determination time (C169)
State
ON
Multistage position is defined by combination of
the inputs.
OFF
Example (default input configuration
shown—see
7
6
See I/O specs on
CP2
CP1
0
0
0
1
1
0
1
1
0
0
0
1
1
0
1
1
5
4
Description
page
3–84):
CP3
CP2 CP1
5
4
3
2
1
page 4–6.
L
P24
PCS
PLC