3−102

Output Logic and Timing

Logic Output Function – The inverter has a built-in logic output feature. Select any two
operands out of all intelligent output options except LOG1~LOG3 and their operator out
of AND, OR, or XOR (exclusive OR). The terminal symbol for the new output is [LOG].
Use C021, C022 or C026 to route the logical result to terminal [11], [12] or the relay
terminals. LOG1-LOG3, no, OPO cannot be the operand.
Intelligent outputs
used as internal
inputs:
RUN, FA1, FA2,
OL, OD, AL, Dc,
...EDM
RUN, FA1, FA2,
OL, OD, AL, Dc,
...EDM
The following table shows all four possible input combinations with each of the three
available logic operations.
Operand
A
0
0
1
1
C142/C145/C148
Operand A
C143/C146/C149
Operand B
Operator
B
AND
OR
0
0
0
1
0
1
0
0
1
1
1
1
C144/C147/C150
Operator
AND, OR, XOR
XOR
0
1
1
0
C021
11
C022
12
C026
AL1
AL0
AL2