Motor Constants Functions - Hitachi WJ200 Series Instruction Manual

Wj200 series single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

Func.
Name
Code
Logic output 2 operator
C147
Logic output 3 operand A
C148
Logic output 3 operand B
C149
Logic output 3 operator
C150
Input [1] response time
C160
Input [2] response time
C161
Input [3] response time
C162
Input [4] response time
C163
Input [5] response time
C164
Input [6] response time
C165
Input [7] response time
C166
Multistage speed/position
C169
determination time

Motor Constants Functions

Func.
Name
Code
Auto-tuning selection
H001
Motor constant selection
H002
Motor constant selection,
H202
2
motor
nd
Motor capacity
H003
Motor capacity,
H203
2
nd
motor
Motor poles setting
H004
Motor poles setting,
H204
2
motor
nd
"C" Function
Description
Applies a logic function to calculate
[LOG] output state,
Three options:
00...[LOG] = A AND B
01...[LOG] = A OR B
02...[LOG] = A XOR B
All
the
programmable
available for logic (discrete) outputs
except LOG1 to LOG3, OPO, no
Applies a logic function to calculate
[LOG] output state,
Three options:
00...[LOG] = A AND B
01...[LOG] = A OR B
02...[LOG] = A XOR B
Sets response time of each input
terminal, set range:
0 (x 2 [ms]) to 200 (x 2 [ms])
(0 to 400 [ms])
Set range is 0. to 200. (x 10ms)
"H" Function
Description
Three option codes:
00...Disabled
01...Enabled with motor stop
02...Enabled with motor rotation
Four option codes:
00...Hitachi standard motor
02...Auto tuned data
Eleven selections:
0.1/0.2/0.4/0.75/1.5/2.2/3.7/
5.5/7.5/11/15/18.5
Four selections:
2 / 4 / 6 / 8 / 10
Run
Mode
Lnitial
Edit
data
00
functions
00
01
00
Run
Defaults
Mode
Lnitial
Edit
data
00
00
00
Specified by
the capacity
of each
inverter
model
4
4
C−25
Defaults
Units
1.
1.
1.
1.
1.
1.
1.
0.
ms
Units
-
-
-
kW
kW
poles
poles