Fru Related - Fujitsu PRIMEQUEST 2000 Series Message Reference

Hide thumbs Also See for PRIMEQUEST 2000 Series:
Table of Contents

Advertisement

MMB Messages
Error was detected in the communication with the BMC during the Private LAN monitoring.
Corrective action:
The system board must be replaced. If the error persists, the active MMB must be replaced.
Severity:
Error
286F04FF
Sensor failure
Meaning:
The temperature sensor has failed.
Corrective action:
・For OPL Inlet Temp, the target OPL must be replaced.
・For PCIeSW# [0-1]Temp of IOU# [0-3], the target IOU# [0-3] must be replaced.
・For Inlet Temp of PCI_Box# [0-1], the target PCI_Box# [0-1] must be replaced.
・For PCIeSW# [0-1]Temp of PCI_Box# [0-1], the target PCI_Box# [0-1] must be replaced.
Severity:
Error

2.1.11 FRU related

The FRU related messages are listed below.
2B6F0200
Hardware is incompatible
Meaning:
An unsupported board has been mounted.
Corrective action:
Replace with a system compatible board.
Severity:
Error
2C6F00FF
FRU Not Installed
Meaning:
The component is not mounted.
Corrective action:
No action is necessary.
Severity:
Info
2C6F01FF
FRU Inactive
Meaning:
The component has stopped operating.
Corrective action:
No action is necessary.
Severity:
Info
2C6F02FF
FRU Activation Requested
Meaning:
Addition of the component has been requested.
Corrective action:
No action is necessary.
Severity:
Info
C122-E178-02EN
27

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents