Installation And Maintenance; Installation Precautions; Maintenance; Testing Of The Safety Functions - ABB Tina 7A Original Instructions Manual

Adaptor unit
Table of Contents

Advertisement

4

Installation and maintenance

Installation precautions

First attach the unit on a 35 mm DIN rail. Then attach the safety-loop to the connection block (nr 6-9). Finally,
attach the cables to the connection block (nr 1-5).
Warning! All the safety functions must be tested before starting up the system.

Maintenance

Warning!
The safety functions and the mechanics shall be tested regularly, at least once every year to confirm that all the
safety functions are working properly (EN 62061:2005).
In case of breakdown or damage to the product, contact the nearest ABB/Jokab Safety Service Office or reseller.
Do not try to repair the product yourself since it may accidentally cause permanent damage to the product,
impairing the safety of the device which in turn could lead to serious injury to personnel.

Testing of the safety functions

Make sure the safety unit is working properly by following these steps:
Interrupt the dynamic safety circuit before this unit. The LED should flash between green and red.
Interrupt protection. The LED should light red.
The LED should light green when protection is OK and if the safety circuit(s) before this unit is not
interrupted.

Troubleshooting

LED indication
Lights red
No lights
Lights green (but no dynamic output
detected)
Weak lights or red and green lights at the
same time
Warning! Replace defected unit with a new one and never bypass the safety circuit using Tina 1A or any other
solution.
2TLC172139M0201, rev. B
2013-03-02
Expected causes of faults
Sensor open
Bad connection between loops
24 VDC input to pin-2 (no dynamic signal)
Loss of power supply
Defected dynamic signal input to unit
(asymmetric pulses)
The unit is defect
8
Checking and measures to take
Check status of the sensor
Check terminals at the unit
Check if there is 24 VDC to input (pin-2). If
Yes, check cable or unit before and fix it.
Check 24 VDC / 0 VDC power supply
Check the dynamic input or the unit before
The unit needs to be replaced. Contact
ABB/Jokab Safety.
www.abb.com/ jokabsafety