Heat pump, Split, single service
Line
Function
Inputs / outputs test
7700 I
Relay test
This consists of instructing the regulator's relays one by one and checking their outputs. This enables you to check
that the relays are working and that the cabling is correct. Check that each appliance in the installation is operating
correctly.
– No test _ Everything is on STOP _ Relay output QX23, QX22, QX21 module 1 _ Relay output QX1 to
QX6 _ Relay output QX23, QX21, QX22 module 2 _ Relay output QX7
The display shows the "Key" symbol. Pressing the Info button displays "Error 368"
Warning: The component being tested is receiving electrical power throughout the test.
7710 I
Output (Ux) test
7711 I
Voltage (Ux) value
7720 I
Digital outputs test
7721 I
Digital output DO1
7722 I
Digital output DO2
7730 I
Outside temperature (B9)
7820 I
Sensor temperature BX1
7823 I
Sensor temperature BX4
7824 I
Sensor temperature BX5
7830 I
Sensor temperature BX21 module 1
7831 I
Sensor temperature BX22 module 1
7832 I
Sensor temperature BX21 module 2
7833 I
Sensor temperature BX22 module 2
7841 I
Contact status H1
7846 I
Contact status H2
7855 I
Contact status H3
7914 I
Input EX4
7915 I
Input EX5
7916 I
Input EX6
Etat
8000 I
State heating circuit 1
8001 I
State heating circuit 2
8003 I
State DHW
8004 I
State cooling circuit 1
8006 I
State heat pump
8011 I
State swimming pool
8022 I
State supplementary source
8050 I
History 1
8052 I
History 2
8054 I
History 3
8056 I
History 4
Installation and operating manual "1350-EN"
Setting range
or display
--- , 0 ... 100 %
0 ... 10 Volt
0 = No test
1 = Everything is on STOP
2 = Digital output DO1
3 = Digital output DO
Cooling regime,
Heating regime
Off, ON
-50 ... 50 °C
-28 ... 350 °C
-28 ... 350 °C
-28 ... 350 °C
-28 ... 350 °C
-28 ... 350 °C
-28 ... 350 °C
-28 ... 350 °C
Open, Closed
Open, Closed
Open, Closed
0, 230 V
0, 230 V
0, 230 V
Time, Date, State code
Time, Date, State code
Time, Date, State code
Time, Date, State code
Setting
Basic
setting
increment
No test
1
---
0
No test
Heating
regime
ON
0
0
0
0
0
0
0
0
Open
Open
Open
0
0
0
0
0
0
0
0
0
0
43

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents