Check code
Outdoor 7-segment display
Sub-code
A02
—
A04
—
Note:
The above check codes are examples only, and different check codes may be displayed depending on
the outdoor unit configuration (e.g. a Super heat recovery multi system).
For details, see the service manual for the outdoor unit.
TCC-LINK
central control
Typical fault site
or main remote
controller
display
Water temperature decrease
A02
error
Plate type heatexchanger
A04
freezing protective operation
• Check the water temperature.
• Check the heat insulator of wate pipes.
• Check the line heater.
• Check the PMV coil and PMV.
• Check the 2way valve coil and 2way valve.
– 43 –
Indoor unit (including Hot Water Module)
Description of error