Toshiba MMW-AP0271LQ-E Service Manual page 49

Hot water module
Hide thumbs Also See for MMW-AP0271LQ-E:
Table of Contents

Advertisement

Check code
Main
Outdoor 7-segment display
remote
Check
Sub-code
controller
code
F03
F04
F04
F05
F05
01:
TE1 sensor
error
F06
F06
02:
TE2 sensor
error
F07
F07
F08
F08
F10
F11
F12
F12
01: Compressor
1 side
02: Compressor
F13
F13
2 side
03: Compressor
3 side
Location
Description
of
detection
Indoor
Indoor TC1
unit
sensor error
I/F
TD1 sensor
error
I/F
TD2 sensor
error
I/F
TE1/TE2
sensor error
I/F
TL sensor error All stop
I/F
TO sensor error All stop
Indoor unit
Indoor TA
sensor error
Indoor unit
Indoor TF
sensor error
I/F
TS1 sensor
error
IPDU
TH sensor error All stop
Error detection
System status
condition(s)
Stop of
Sensor resistance is infinity
corresponding unit
or zero (open / short circuit).
All stop
Sensor resistance is infinity
or zero (open / short circuit).
All stop
Sensor resistance is infinity
or zero (open / short circuit).
All stop
Sensor resistance is infinity
or zero (open / short circuit).
Sensor resistance is infinity
or zero (open / short circuit).
Sensor resistance is infinity
or zero (open / short circuit).
Stop of
Sensor resistance is infinity
corresponding unit
or zero (open / short circuit).
Stop of
Sensor resistance is infinity
corresponding unit
or zero (open / short circuit).
All stop
Sensor resistance is infinity
or zero (open / short circuit).
Sensor resistance is infinity
or zero (open / short circuit).
– 49 –
Indoor unit (including Hot Water Module)
Check items (locations)
• Check connection of TC1
sensor connector and
wiring.
• Check resistance
characteristics of TC1
sensor.
• Check for defect in indoor
P.C. board.
• Check connection of TD1
sensor connector.
• Check resistance
characteristics of TD1
sensor.
• Check for defect in outdoor
P.C. board (I/F).
• Check connection of TD2
sensor connector.
• Check resistance
characteristics of TD2
sensor.
• Check for defect in outdoor
P.C. board (I/F).
• Check connection of TE1/
TE2 sensor connectors.
• Check resistance
characteristics of TE1/TE2
sensors.
• Check for defect in outdoor
P.C. board (I/F).
• Check connection of TL
sensor connector.
• Check resistance
characteristics of TL
sensor.
• Check for defect in outdoor
P.C. board (I/F).
• Check connection of TO
sensor connector.
• Check resistance
characteristics of TO
sensor.
• Check for defect in outdoor
P.C. board (I/F).
• Check connection of TA
sensor connector and
wiring.
• Check resistance
characteristics of TA
sensor.
• Check for defect in indoor
P.C. board.
• Check connection of TF
sensor connector and
wiring.
• Check resistance
characteristics of TF
sensor.
• Check for defect in indoor
P.C. board.
• Check connection of TS1
sensor connector.
• Check resistance
characteristics of TS1
sensor.
• Check for defect in outdoor
P.C. board (I/F).
• Defect in IGBT built-in
temperature sensor
Replace A3-IPDU P.C.
board.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmw-ap0561lq-eMmw-ap0271lq-trMmw-ap0561lq-tr