Toshiba MMW-AP0271LQ-E Service Manual page 51

Hot water module
Hide thumbs Also See for MMW-AP0271LQ-E:
Table of Contents

Advertisement

Check code
Main
Outdoor 7-segment display
remote
Check
Sub-code
controller
code
01: Compressor
1 side
02: Compressor
2 side
03: Compressor
3 side
H02
H02
01: Compressor
1 side
02: Compressor
H03
H03
2 side
03: Compressor
3 side
H05
H05
H06
H06
H07
H07
Location
Description
of
detection
IPDU
Compressor
error (lockup)
MG-CTT error
IPDU
Current
detection circuit
error
I/F
TD1 sensor
miswiring
(incomplete
insertion)
I/F
Activation of
low-pressure
protection
I/F
Low oil level
protection
Error detection
System status
condition(s)
All stop
Overcurrent is detected
several seconds after
startup of inverter
compressor.
All stop
Current flow of at least
specified magnitude is
detected despite inverter
compressor having been
shut turned off.
All stop
Discharge temperature of
compressor 1 (TD1) does
not increase despite
compressor being in
operation.
All stop
Low-pressure Ps sensor
detects operating pressure
lower than 0.02 MPa.
All stop
Operating compressor
detects continuous state of
low oil level for about 2
hours.
– 51 –
Indoor unit (including Hot Water Module)
Check items (locations)
• Check for defect in
compressor.
• Check power supply
voltage. (AC200 V ± 10 %).
• Check compressor system
wiring, particularly for open
phase.
• Check connection of
connectors / terminals on
A3-IPDU P.C. board.
• Check conductivity of case
heater.
(Check for refrigerant
entrapment inside
compressor.)
• Check for defect in outdoor
P.C. board (A3-IPDU).
• Check outdoor MG-CTT.
• Check current detection
circuit wiring.
• Check defect in outdoor
P.C. board (A3-IPDU).
• Check installation of TD1
sensor.
• Check connection of TD1
sensor connector and
wiring.
• Check resistance
characteristics of TD1
sensor.
• Check for defect
• Check service valves to
confirm full opening
(both gas and liquid sides).
• Check outdoor PMVs for
clogging (PMV1, 2).
• Check for defect in SV2 or
SV4 circuits.
• Check for defect in low
pressure Ps sensor.
• Check indoor filter for
clogging.
• Check valve opening status
of indoor PMV.
• Check refrigerant piping for
clogging.
• Check operation of outdoor
fan (during heating).
• Check for insufficiency in
refrigerant quantity.
<All outdoor units in
corresponding line to be
checked>
• Check balance pipe
service valve to confirm full
opening.
• Check connection and
installation of TK1, TK2,
TK3, TK4, and TK5
sensors.
• Check resistance
characteristics of TK1,
TK2, TK3, TK4, and TK5
sensors.
• Check for gas or oil leak in
same line.
• Check for refrigerant
entrapment inside
compressor casing.
• Check SV3A, SV3B, SV3C,
SV3D, SV3E, and SV3F
valves for defect.
• Check oil return circuit of
oil separator for clogging.
• Check oil equalizing circuit
for clogging.
MG-CTT: Magnet contactor