Toshiba MMW-AP0271LQ-E Service Manual page 60

Hot water module
Hide thumbs Also See for MMW-AP0271LQ-E:
Table of Contents

Advertisement

Errors detected by TCC-LINK central control device
Check code
Main
Outdoor 7-segment display
remote
Sub-code
controller
C05
C06
C12
Differs according to
nature of alarm-causing
error
P30
(L20 displayed.)
Location
Description
of
detection
TCC-LINK
TCC-LINK
central control
device
transmission
error
TCC-LINK
central control
device reception
error
General-
Blanket alarm
purpose
for general-
device
purpose device
I/F
control interface
TCC-LINK
Group control
follower unit
error
Duplicated
central control
address
Error detection
System status
condition(s)
Continued
Central control device is
operation
unable to transmit signal.
Continued
Central control device is
operation
unable to receive signal.
Continued
Error signal is input to
operation
control interface for general-
purpose devices.
Continued
Error occurs in follower unit
operation
under group control.
([P30] is displayed on central
control remote controller.)
Continued
There is duplication in
operation
central control addresses.
– 60 –
Indoor unit (including Hot Water Module)
Check items (locations)
• Check for defect in central
control device.
• Check for defect in central
control communication line.
• Check termination
resistance setting.
• Check for defect in central
control device.
• Check for defect in central
control communication
line.
• Check termination
resistance setting.
• Check power supply for
devices at other end of
central control
communication line.
• Check defect in P.C.
boards of devices at other
end of central control
communication line.
• Check error input.
• Check check code of unit
that has generated alarm.
• Check address settings.