Check code
Main
Outdoor 7-segment display
remote
Check
Sub-code
controller
code
H25
H25
L02
L02
L03
L04
L04
L05
No. of priority
indoor units
L06
L06
L07
L08
L08
L09
L10
L10
Target indoor
address
L17
L17
L18
L18
Location
Description
of
detection
I/F
TD3 sensor
miswiring
(incomplete
insertion)
Indoor
Outdoor unit
unit
model mismatch
error
Indoor
Duplicated
unit
indoor header
unit
I/F
Duplicated
outdoor line
address
I/F
Duplicated
priority indoor
unit (as
displayed on
priority indoor
unit)
I/F
Duplicated
priority indoor
unit (as
displayed on
indoor unit other
than priority
indoor unit)
Indoor unit
Connection of
group control
cable to
standalone
indoor unit
Indoor unit
Indoor group /
addresses not
set
Indoor unit
Indoor capacity
not set
I/F
Outdoor
capacity not set
I/F
Outdoor unit
model mismatch
error
I/F
Cool / heat
switch unit error
Error detection
System status
condition(s)
All stop
Air discharge temperature
(TD3) does not increase
despite compressor 3 being
in operation.
Only the target
An error was found on the
unit stopped
outdoor unit model.
Stop of
There is more than one
corresponding unit
header unit in group.
All stop
There is duplication in line
address setting for outdoor
units belonging to different
refrigerant piping systems.
All stop
More than one indoor unit
has been set up as priority
indoor unit.
All stop
More than one indoor unit
have been set up as priority
indoor unit.
Stop of
There is at least one stand-
corresponding unit
alone indoor unit to which
group control cable is
connected.
Stop of
Address setting has not
corresponding unit
been performed for indoor
units.
Stop of
Capacity setting has not
corresponding unit
been performed for indoor
unit.
All stop
Jumper wire provided on
P.C. board for servicing
I/F P.C. board has not been
removed as required for
given model.
The outdoor unit model is
duplicate. The Cool/Heat
Flex series 1/2 are duplicate.
Only the target
The heating operation was
unit stopped
performed without the
coolonly setting configured
in a cool-only room where a
cool / heat switch unit is not
connected.
– 54 –
Indoor unit (including Hot Water Module)
Check items (locations)
• Check installation of TD3
sensor.
• Check connection of TD3
sensor connector and
wiring.
• Check resistance
characteristics of TD3
sensor.
• Check for defect in outdoor
P.C. board (I/F).
• Check the model name of
the outdoor unit.
• Check the miswiring of the
communication line
between indoor and
outdoor.
• Check indoor addresses.
• Check for any change
made to remote controller
connection (group /
individual) since indoor
address setting.
• Check line addresses.
• Check display on priority
indoor unit.
• Check displays on priority
indoor unit and outdoor
unit.
• Check indoor addresses.
• Check indoor addresses.
Note:
This code is displayed
when power is turned on
for the first time after
installation.
Set indoor capacity.
(DN = 11)
Check model setting of P.C.
board for servicing outdoor
I/F P.C. board.
• Check the outdoor unit
model.
• Check the remote controller
setting. (DN="0F")
• Check the cool / heat
switching unit.
Check the piping
connection of the switching
unit.
(Miswiring of discharge
gas / suction gas)
Check the SVS / SVD
valve miswiring /
misinstallation.