Chapter 7
Settings and configuration
112
Third sequence setting current (3rd Set Ie)
Set the current for the third parameter group.
Press Store to save the value.
This parameter will only be displayed if parameter
No of Seq is set to 3.
Function of first programmable input (In0)
This parameter will automatically be set as Start2.
Function of second programmable input (In1)
This parameter will automatically be set as Start3.
Overload
The overload protection is not activated when sequence start
is selected.
To activate the motor overload protection enter this group
and change to required function.
The overload protection can normally not be used when
starting several motors since the total starting time will
become too long and the protection will trip.
First sequence parameters (1st Seq .Param.)
To set parameters related to the first sequence, enter the 1st
Seq. Param. group.
Following parameters can be adjusted:
1st Set Ie
Setting current.
Start Ramp1 Ramp time for start
Init Volt1
Initial voltage.
Curr Lim1
Current limit level.
Press Store to save the selected parameter.
1SFC132003M0201